Fisherr FIELDVUE™ DVC6000 SIS Digital ValveControllers for Safety Instrumented System (SIS)Solutions Instruction Manual(Supported)Supported products m
DVC6000 SISSeptember 20131-2Table 1-1. FIELDVUE DVC6000 SIS CapabilitiesAuto CalibrationCustom CharacterizationAlertsStep Response, Drive Signal Test
DVC6000 SISSeptember 20135-12PST Calibration (1-3-5)Access PST Calibration by selecting PST Calibrationfrom the Calibrate menu. Follow the prompts on
Viewing Device Variables and DiagnosticsSeptember 20136-16-6Section 6 Viewing Device Variables and DiagnosticsService Tools 6-2...
DVC6000 SISSeptember 20136-2Service ToolsAlert Conditions (2-1)Instrument Alert Conditions, when enabled, detectmany operational and performance issue
Viewing Device Variables and DiagnosticsSeptember 20136-3sensor reading is outside of the range of −40 to 85C(−40 to 185F). The temperature reading
DVC6000 SISSeptember 20136-4indicates the status of the Operational items listedbelow. The status of more than one operational itemmay be indicated.In
Viewing Device Variables and DiagnosticsSeptember 20136-5PRESS TO PERFORMTHE CONFIGUREDPARTIAL STROKETESTFigure 6-1. Local Control PanelDevice (Digita
DVC6000 SISSeptember 20136-6Example — 18AWG Shielded Audio, Control andInstrumentation CableManufacturer’s specifications include:Nom. Characteristic
Viewing Device Variables and DiagnosticsSeptember 20136-7Connect a 24 VDC power supply to the solenoidvalve and a second 24 VDC power supply to theDVC
DVC6000 SISSeptember 20136-81. When allowed by the Logic Solver, momentarilyremove and then restore power to the solenoid(typically 100 to 200 millis
Viewing Device Variables and DiagnosticsSeptember 20136-9NoteDo not use the following raw travelinput indication for calibrating thetravel sensor. The
Introduction and SpecificationsSeptember 20131-3testing methods, which reduce testing andmaintenance time, improve system performance, andprovide diag
DVC6000 SISSeptember 20136-106
Maintenance and TroubleshootingSeptember 20137-17-7Section 7 Maintenance and TroubleshootingModule Base MaintenanceRemoving the Module Base 7-4...
DVC6000 SISSeptember 20137-2The DVC6000 SIS digital valve controller enclosure israted NEMA 4X and IP66, therefore periodic cleaningof internal compon
Maintenance and TroubleshootingSeptember 20137-3 Ensure that all caps and coversare correctly installed before puttingthis unit back into service. Fa
DVC6000 SISSeptember 20137-4Removing the Module Base To remove the module base perform the followingsteps. Refer to figures 8-1, 8-2, 8-3, and 8-4 fo
Maintenance and TroubleshootingSeptember 20137-54. Insert the module base (key 2) into the housing(key 1).5. Install three socket head screws (key 3
DVC6000 SISSeptember 20137-6Figure 7-3. I/P ConverterW9328-1SOCKET-HEADSCREWS (4)(KEY 23)SHROUD(KEY 169)I/P CONVERTER(KEY 41)BOOTS(KEY 210)5. Reinsta
Maintenance and TroubleshootingSeptember 20137-7Figure 7-4. DIP Switch LocationBACK OF PWB ASSEMBLYSUB-MODULEDIP SWITCHUPDOWNTRAVEL SENSORCONNECTORTER
DVC6000 SISSeptember 20137-8Gauges, Pipe Plugs, or Tire Valves Depending on the options ordered, the DVC6000 SISdigital valve controller will be equi
Maintenance and TroubleshootingSeptember 20137-97. Apply silicone lubricant to the O-ring (key 36) andinstall the O-ring over the 2-5/8 inch threads
DVC6000 SISSeptember 20131-4Table 1-2. SpecificationsAvailable ConfigurationsValve-Mounted InstrumentsDVC6010 SIS: Sliding-stem applicationsDVC6020 SI
DVC6000 SISSeptember 20137-10b. Disconnect the three potentiometer assemblywires from the terminal.7. Remove the screw (key 72) that fastens the trav
Maintenance and TroubleshootingSeptember 20137-11NOTE: THE POTENTIOMETER RESISTANCE BETWEEN PINS 2 AND 3 CAN BEMEASURED AT THE CONNECTOR. INSERT
DVC6000 SISSeptember 20137-12DVC6020 SIS Digital Valve Controller andDVC6025 Remote Feedback UnitRefer to figure 8-2 for DVC6020 SIS and 8-7 forDVC602
Maintenance and TroubleshootingSeptember 20137-13Figure 7-7. FIELDVUE DVC6020 SIS Bias Spring (key 82)InstallationBIAS SPRING(KEY 82)ARM ASSEMBLY(KEY
DVC6000 SISSeptember 20137-1411. While observing the resistance, tighten the screw(key 80) to secure the feedback arm to the travelsensor shaft. Be s
Maintenance and TroubleshootingSeptember 20137-15LOOP + / TEST +TEST −DCS SYSTEM (OR OTHERCURRENT SOURCE)4−20mACURRENTSOURCE+−LOOP −LOOP + / TEST +LOO
DVC6000 SISSeptember 20137-16Table 7-3. Instrument Troubleshooting Symptom Possible Cause Action1. Analog input reading atinstrument does not matchac
Maintenance and TroubleshootingSeptember 20137-17Table 7-3. Instrument Troubleshooting (Continued)Symptom ActionPossible Cause3h. Configuration errors
DVC6000 SISSeptember 20137-18DVC6000 SIS Troubleshooting Checklist1. Instrument serial number as read from nameplate ________________________________
PartsSeptember 20138-18-8Section 8 PartsParts Ordering 8-2...Parts Kits 8-2...
Introduction and SpecificationsSeptember 20131-5Table 1-2. Specifications (continued)Electromagnetic Interference (EMI)Meets EN 61326-1 (First Edition
DVC6000 SISSeptember 20138-2Parts Ordering Whenever corresponding with your Emerson ProcessManagement sales office about this equipment,always mentio
PartsSeptember 20138-3Kit Description Part Number11 Adjustment Arm Kit(includes washer, nut and adjustment arm) 14B5072X13212* PTFE Sleeve Kit[For po
DVC6000 SISSeptember 20138-4Parts ListParts which do not show part numbers are notorderable as individual parts. In most cases, they areavailable in o
PartsSeptember 20138-5Key Description Part NumberTerminal Box DVC6010 SIS, DVC6020 SIS, DVC6030 SIS,DVC6005 SIS (see figures 8-1, 8-2, 8-3, and 8-4)4
DVC6000 SISSeptember 20138-6Key Description Part NumberDVC6020 SIS and DVC6025 (see figure 8-2 and 8-7)74 Mounting Bracket82 Bias Spring, SST(3)83 Be
PartsSeptember 20138-7Figure 8-1. FIELDVUE DVC6010 SIS Digital Valve Controller Assembly APPLY LUB, SEALANTSECTION A‐ASECTION E‐EEESECTION D‐D11NOT
DVC6000 SISSeptember 20138-8Figure 8-2. FIELDVUE DVC6020 SIS Digital Valve Controller Assembly APPLY LUB, SEALANTSECTION B‐BSECTION C‐CSECTION A‐AS
PartsSeptember 20138-9Figure 8-2. FIELDVUE DVC6020 SIS Digital Valve Controller Assembly (continued) APPLY LUB, SEALANTNOTES:SEE FIGURE 8-5 FOR GAU
DVC6000 SISSeptember 20138-10NOTES:SEE FIGURE 8-5 FOR GAUGE CONFIGURATIONS2. APPLY LUBRICANT KEY 65 TO ALL O-RINGS UNLESS OTHERWISE SPECIFIEDFigure 8-
PartsSeptember 20138-11Figure 8-4. FIELDVUE DVC6005 SIS Base Unit APPLY LUB, SEALANTSECTION A‐ANOTES:1. APPLY LUBRICANT KEY 65 TO ALL O-RINGS UNLES
DVC6000 SISSeptember 20131-6Table 1-2. Specifications (continued)ConnectionsSupply Pressure: 1/4 NPT internal and integralpad for mounting 67CFR regul
DVC6000 SISSeptember 20138-12Figure 8-4. FIELDVUE DVC6005 SIS Base Unit (continued) APPLY LUB, SEALANTNOTES:SEE FIGURE 8-5 FOR GAUGE CONFIGURATIONS
PartsSeptember 20138-13Figure 8-5. Typical FIELDVUE DVC6000 SIS / DVC6005 SIS Base Unit Gauge Configuration APPLY LUB, SEALANTSINGLE-ACTING DIRECT
DVC6000 SISSeptember 20138-14Figure 8-7. FIELDVUE DVC6025 Feedback Unit Assembly49B7987-A/ILNOTE: 1. APPLY LUBRICANT KEY 65 TO ALL O-RINGS UNLESS OTHE
PartsSeptember 20138-15Figure 8-8. FIELDVUE DVC6035 Feedback Unit Assembly49B7988-ANOTE: 1. APPLY LUBRICANT KEY 65 TO ALL O-RINGS UNLESS OTHERWISE SPE
DVC6000 SISSeptember 20138-168
Principle of OperationSeptember 2013A-1A-A-Appendix A Principle of OperationHART Communication A-2...Di
DVC6000 SISSeptember 2013A-2Figure A-1. HART Frequency Shift Keying Technique−0.5 V+0.5 V1200 Hz“1”2200 Hz“0”AVERAGE CURRENT CHANGE DURING COMMUNICATI
Principle of OperationSeptember 2013A-3Figure A-3. FIELDVUE DVC6000 SIS Digital Valve Controller Block DiagramE0408INPUT SIGNAL4−20 mA+HARTSUPPLY PRES
DVC6000 SISSeptember 2013A-4TRAVEL SENSORTERMINAL BOXTERMINAL BOX COVERMODULE BASE ASSEMBLYPRINTED WIRING BOARD ASSEMBLYI/P CONVERTERPNEUMATIC RELAYHO
Loop Schematics/NameplateSeptember 2013B-1B-B-Appendix B Loop Schematics/Nameplates B
Introduction and SpecificationsSeptember 20131-7Related DocumentsOther documents containing information related toDVC6000 SIS digital valve controller
DVC6000 SISSeptember 2013B-2This section includes loop schematics required forwiring of intrinsically safe installations. It also containsthe approval
Loop Schematics/NameplateSeptember 2013B-3Figure B-3. CSA Schematic for FIELDVUE DVC6005 SIS with DVC6015, DVC6025, and DVC60351 SEE NOTES IN FIGUR
DVC6000 SISSeptember 2013B-4Figure B-6. FM Schematic for FIELDVUE DVC6010 SIS, DVC6020 SIS, and DVC6030 SIS Digital Valve ControllersGE42819 Sheet 2,
Loop Schematics/NameplateSeptember 2013B-5NOTES THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT
DVC6000 SISSeptember 2013B-6GE60771 sheet 3, Rev. B1 SEE NOTES IN FIGURE B-1311Figure B-10. ATEX Loop Schematic For FIELDVUE DVC6010 SIS, DVC6020 S
Loop Schematics/NameplateSeptember 2013B-7GE60771 sheet 6, Rev. B1 SEE NOTES IN FIGURE B-13111Figure B-12. ATEX Loop Schematic for DVC6005 SIS with
DVC6000 SISSeptember 2013B-8DVC6010 SIS, DVC6020 SIS, DVC6030 SIS, DVC6005 SISFigure B-14. Typical ATEX Nameplates; FlameproofDVC6015, DVC6025, DVC603
Loop Schematics/NameplateSeptember 2013B-9GE42990 Sheet 2, Rev. E1 SEE NOTES IN FIGURE B-1811Figure B-16. IECEx Loop Schematic for FIELDVUE DVC6010
DVC6000 SISSeptember 2013B-10GE42990 Sheet 8, Rev.NOTES THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPAR
GlossarySeptember 2013Glossary-1GlossaryAlert PointAn adjustable value that, when exceeded,activates an alert.AlgorithmA set of logical steps to solve
DVC6000 SISSeptember 20131-8Table 1-3. Electromagnetic Immunity PerformancePort Phenomenon Basic Standard Test LevelPerformance Criteria(1)Point-to-Po
DVC6000 SISSeptember 2013Glossary-2ControllerA device that operates automatically to regulate acontrolled variable.Crossover PointThe point at which t
GlossarySeptember 2013Glossary-3Feedback SignalIndicates to the instrument the actual position ofthe valve. The travel sensor provides thefeedback sig
DVC6000 SISSeptember 2013Glossary-4Leak ClassDefines the allowable leakage by a valve when itis closed. Leak class numbers are listed in twostandards:
GlossarySeptember 2013Glossary-5Quick OpeningA valve flow characteristic where most of thechange in flow rate takes place for small amountsof stem tra
DVC6000 SISSeptember 2013Glossary-6Travel Alert High PointValue of the travel, in percent of ranged travel,which, when exceeded, sets the Travel Alert
GlossarySeptember 2013Glossary-7Watch Dog TimerA timer that the microprocessor must rearmperiodically. If the microprocessor is unable torearm the tim
DVC6000 SISSeptember 2013Glossary-8Glossary
IndexSeptember 2013Index-1IndexAAction on Failed Test, 4-22Actuator Style, 4-19adjustment arm, 2-7Alert Conditions, 6-2Alert Record, 6-3Electronics, 6
DVC6000 SISSeptember 2013Index-2Sensor Calibration, 5-6Pressure Sensors, 5-6TravelAuto, 5-3Manual, 5-4Analog Calibration Adjust, 5-4Digital Calibratio
IndexSeptember 2013Index-3End Point Pressure Deviation, 6-3Environment Alerts, 4-14EPPC Saturation Time, 4-11EPPC Set Point, 4-11Error Messages, Auto
Introduction and SpecificationsSeptember 20131-9Table 1-5. Hazardous Area Classifications—FM (United States)CertificationBodyType Certification Obtain
DVC6000 SISSeptember 2013Index-4LLag Time, 4-13Last AutoCal Status, 4-19Last Calibration Type, 4-19LCP100 (Local Control Panel), 2-35LCP100 Local Cont
IndexSeptember 2013Index-5PartsCommon Parts, 8-4Feedback Parts, 8-5Gauges, Tire Valves, & Pipe Plugs, 8-5I/P Converter Assembly, 8-4Kits, 8-2Modul
DVC6000 SISSeptember 2013Index-6SISPressure Mode Enable, 4-11Valve Stuck Alert, 4-23SIS Alerts, 4-16SIS Panel Comm Error, 6-3Solenoid Valve, Health Mo
IndexSeptember 2013Index-7Tuning, 4-4Pressure, 4-9Travel, 4-4Tuning SetPressure, 4-9Travel, 4-4Tuning SetsPressure, 4-9Gain Values, 4-9Travel, 4-4Gain
DVC6000 SISSeptember 2013Index-8Index
Emerson Process ManagementMarshalltown, Iowa 50158 USASorocaba, 18087 BrazilChatham, Kent ME4 4QZ UKDubai, United Arab EmiratesSingapore 128461 Singap
DVC6000 SISSeptember 20131-10Table 1-6. Hazardous Area Classifications—ATEXCertificate Type Certification Obtained Entity Rating Temperature CodeEnclo
Introduction and SpecificationsSeptember 20131-11Table 1-7. Hazardous Area Classifications—IECExCertificate Type Certification Obtained Entity Rating
DVC6000 SISSeptember 20131-121
InstallationSeptember 20132-12-2Section 2 InstallationHazardous Area Classifications and Special Instructions for “Safe Use” and Installations in Haza
DVC6000 SISSeptember 20132-2Wiring PracticesLogic Solver or Control System Requirements 2-28...Voltage Available 2-28...
InstallationSeptember 20132-3InstallationThe DVC6000 SIS can be used with either air ornatural gas as the supply medium. If using natural gasas the pn
DVC6000 SISSeptember 20132-4In addition to remote venting of theunit, ensure that all caps and coversare correctly installed. Failure to doso could re
InstallationSeptember 20132-5FlameproofOperating ambient temperature: −52C or −40C to + 85CRefer to table 1-6 for additional approval information,a
DVC6000 SISSeptember 20132-6/OCCAP SCREW, FLANGEDMACHINE SCREWSHIELDADJUSTMENT ARMCONNECTOR ARMCAP SCREWPLAIN WASHERFigure 2-1. FIELDVUE DVC6010 SIS D
InstallationSeptember 20132-7CAP SCREW, FLANGEDMACHINE SCREW,FLAT HEADSHIELDADJUSTMENT ARMCONNECTOR ARMPLAIN WASHERMACHINE SCREWMACHINE SCREW,LOCK WAS
DVC6000 SISSeptember 20132-8A7209-1SPRING RELAXEDSPRING UNDER TENSION OFADJUSTMENT ARM PINFEEDBACK ARMADJUSTMENTARM PINBIASSPRINGBIAS SPRINGFigure 2-3
InstallationSeptember 20132-9PLAIN WASHERHEX NUTSTUD, CONT THREADALOCK WASHERCAP SCREWMOUNTING PLATECAP SCREW, HEXSOCKETVENTPLAIN WASHERHEX NUTSTUD, C
Introduction and SpecificationsInstallationBasic SetupDetailed SetupCalibrationViewing Device Variables and DiagnosticsMaintenance and Troubleshooting
DVC6000 SISSeptember 20132-10CAP SCREW, HEX SOCKETCAMFOLLOWER ARMEXTENSIONMACHINE SCREW,LOCK WASHER,HEX NUTCAP SCREW29B1673-AFigure 2-6. FIELDVUE DVC6
InstallationSeptember 20132-1119B3879−AMOUNTING BRACKETTRAVEL INDICATORTRAVELINDICATOR PINFEEDBACK ARMSPACER29B1703-AFigure 2-8. Mounting a FIELDVUE D
DVC6000 SISSeptember 20132-1219B3879-ASTARTING POSITION OF THE ACTUATOR TRAVELINDICATOR ASSEMBLY IF INCREASING PRESSUREFROM OUTPUT A DRIVES THE INDICA
InstallationSeptember 20132-13FEEDBACK ARMBIAS SPRINGTRAVEL INDICATOR PIN48B4164-BHOLE AHOLE BFigure 2-11. Positioning Travel Indicator Pin in the Fee
DVC6000 SISSeptember 20132-144-INCH 1/4-20 HEX HEAD SCREWSTANDOFFMOUNTING BRACKETPIPESTAND MOUNTINGWALL MOUNTINGMOUNTING BRACKET1-INCH 1/4-20HEX HEAD
InstallationSeptember 20132-159. Slide the adjustment arm pin in the slot of theconnector arm until the pin is in line with the desiredvalve travel m
DVC6000 SISSeptember 20132-16DVC6035 on Quarter-Turn Actuators If ordered as part of a control valve assembly, thefactory mounts the remote feedback
InstallationSeptember 20132-17NOTE:APPLY LUBRICANT11W8077-1 SIS67CFR REGULATORCAP SCREWSO-RINGSUPPLY CONNECTIONFigure 2-15. Mounting the Fisher 67CFR
DVC6000 SISSeptember 20132-18Pressure ConnectionsWARNINGRefer to the Installation WARNING atthe beginning of this section.Pressure connections are sho
InstallationSeptember 20132-19WARNINGWhen using natural gas as the supplymedium, or for explosion proofapplications, the following warningsalso apply:
DVC6000 SISiiFast Key SequenceFunction/VariableFast-KeySequenceCoordinates(1)Function/VariableFast-KeySequenceCoordinates(1)A Minus B 3-5-3 4-G Drive
DVC6000 SISSeptember 20132-20mounted on the actuator mounting boss. Supply andoutput pressure gauges may be supplied on the digitalvalve controller. T
InstallationSeptember 20132-2124/48 VDC 110/220 VAC, etc.Port ACONTROL SIGNAL(4−20 mA, 0−20 mA, 0−24 VDC)Port BSUPPLY PRESSUREMONITORING LINECONTROL L
DVC6000 SISSeptember 20132-22Vent WARNINGPersonal injury or property damagecan occur from cover failure due tooverpressure. Ensure that thehousing ve
InstallationSeptember 20132-23Wiring connections must be inaccordance with local, regional, andnational codes for any given hazardousarea approval. Fa
DVC6000 SISSeptember 20132-24SAFETY GROUNDLOOP−LOOP+EARTH GROUNDTALK+TALK−39B3399-B Sheet 2Figure 2-20. FIELDVUE DVC6000 SIS Digital Valve ControllerT
InstallationSeptember 20132-25FEEDBACK CONNECTIONS TERMINAL BOXFEEDBACK UNITTO FEEDBACK UNIT TERMINAL 3TO FEEDBACK UNIT TERMINAL 2TO FEEDBACK UNIT TER
DVC6000 SISSeptember 20132-26Using an External 10 kOhm ExternalPotentiometer as a Remote Travel Sensor NotePotentiometer travel must be between1.3 and
InstallationSeptember 20132-27NoteThe digital valve controller must beconfigured using the SStem/Rollerselection on the menu of theappropriate setup d
DVC6000 SISSeptember 20132-28Test Connections WARNINGPersonal injury or property damagecaused by fire or explosion may occurif this connection is att
InstallationSeptember 20132-29The voltage available at the instrument is not the voltage measured at the instrument terminals. Once the instrument isc
DVC6000 SISiiiiFast Key SequenceFunction/VariableFast-KeySequenceCoordinates(1)Function/VariableFast-KeySequenceCoordinates(1)Partial Stroke Test 2-5
DVC6000 SISSeptember 20132-30Table 2-1. Cable CharacteristicsCable TypeCapacitance(1)pF/ftCapacitance(1)pF/mResistance(2)Ohms/ftResistance(2)Ohms/mBS5
InstallationSeptember 20132-31Installation in a Safety InstrumentedSystemA DVC6000 SIS instrument may be used in a SafetyInstrumented System (SIS) to
DVC6000 SISSeptember 20132-32NOTES:1/4-18 NPT X 3/8 OD TUBINGELECTRICAL WIRINGDVC6000 SIS DIGITALVALVE CONTROLLERLOGIC SOLVERSUPPLYSINGLE-ACTING SPRIN
InstallationSeptember 20132-33NOTES:1/4-18 NPT X 3/8 OD TUBINGELECTRICAL WIRINGAN AIR SUPPLY LINE IS NEEDED FOR ANEXTERNAL PILOTED SOLENOID VALVE. CON
DVC6000 SISSeptember 20132-34NOTES:1/4-18 NPT X 3/8 OD TUBINGELECTRICAL WIRINGLOGIC SOLVERLC340 LINE CONDITIONERDVC6000 SIS DIGITALVALVE CONTROLLERSIN
InstallationSeptember 20132-35EFX8553G305 103594 or EFX8551G305103594 low-powered solenoid valveswith aluminum bodies can be usedwhere the application
DVC6000 SISSeptember 20132-36NOTE: DO NOT CONNECT THE LOOP + TERMINAL IN THE LCP100 TO THE LOOP + TERMINAL IN THE DVC6000 SIS. THIS WILL CAUSE THE LCP
InstallationSeptember 20132-37NOTE: THE LOGIC SOLVER MINIMUMOUTPUT MUST BE AT LEAST 8 mA. THELCP100, WHEN POWERED BY THE LOOP,CONSUMES APPROXIMATELY 4
DVC6000 SISSeptember 20132-38GE26881-B, Sheet 1E1083-1NOTE:THE LOGIC SOLVER MINIMUM OUTPUT MUST BE ATLEAST 8 mA. THE LCP100, WHEN POWERED BY THE LOOP,
Basic SetupSeptember 20133-13-3Section 3 Basic SetupConfiguration Protection 3-2...Instrument Mode 3-2...
DVC6000 SISiiiiiiResponse Control1 Tuning2 Travel/Pressure Control3 Input Characterization4 Custom Characterization Table5 Dynamic Response
DVC6000 SISSeptember 20133-2Configuration Protection To setup and calibrate the instrument, the protectionmust be set to None with the Field Communica
Basic SetupSeptember 20133-3NoteIn the event of a power failure theDVC6000 SIS automatically restoresthe device to In Service uponrestoration of power
DVC6000 SISSeptember 20133-4Table 3-1. Possible Configurations for a FIELDVUE DVC6000 SIS Digital Valve Controller operated by 4-20 mASetup Wizard Con
Basic SetupSeptember 20133-5actuator model, then you will be prompted for setupparameters such as:Actuator Style (select spring & diaphragm, pisto
DVC6000 SISSeptember 20133-6Performance Tuner (1-1-2) WARNINGDuring performance tuning the valvemay move, causing process fluid orpressure to be relea
Detailed SetupSeptember 20134-14-4Section 4 Detailed SetupMenu and Quick Key Sequence Tables Front Cover...Detailed Setup
DVC6000 SISSeptember 20134-2Detailed SetupThe Detailed Setup selection from the Configure menuallows you to configure the digital valve controller toy
Detailed SetupSeptember 20134-3Table 4-1. Factory Default Detailed Setup Parameters(continued)Setup ParameterDefaultSetting(1)Electronic AlertsShutdow
DVC6000 SISSeptember 20134-4 Change Burst Enable—Turns Burst Mode on andoff. Actual valves are Burst Enable = Disabled(Polled),Enabled. Burst Comman
Detailed SetupSeptember 20134-5Table 4-3. Conditions for Modifying FIELDVUE DVC6000 SIS Digital Valve Controller ParametersParametersIn Service Out of
DVC6000 SISiviv78 910 11ABCDEFGHI12Electronics Alerts1 Drive Current Shutdown2 Drive Signal Alert3 Processor Impaired AlertsTravel Tuning1 Travel Tuni
DVC6000 SISSeptember 20134-6Table 4-3. Conditions for Modifying FIELDVUE DVC6000 SIS Digital Valve Controller Parameters (Continued)ParametersIn Servi
Detailed SetupSeptember 20134-7Table 4-3. Conditions for Modifying FIELDVUE DVC6000 SIS Digital Valve Controller Parameters (Continued)ParametersIn Se
DVC6000 SISSeptember 20134-8Table 4-4. Actuator Information for Basic SetupActuatorManufacturerActuatorModelActuator Size Actuator StyleStartingTuning
Detailed SetupSeptember 20134-9Pressure Tuning (1-2-2-1-3)WARNINGChanges to the tuning set may causethe valve/actuator assembly to stroke.To avoid per
DVC6000 SISSeptember 20134-10Travel/Pressure ControlTvl/Press Cutoffs (1-2-2-2-1) Cutoff Hi—Defines the high cutoff point for thetravel in percent (%
Detailed SetupSeptember 20134-11Table 4-7. Guidelines for Manually Setting Pressure Set PointActuator Type Relay Type Zero Power Condition Partial Str
DVC6000 SISSeptember 20134-12To select an input characterization, select InputCharacterization from the Response Control menu.You can select from the
Detailed SetupSeptember 20134-13NoteLag Time is available in firmware 7, 9,10, and 11. Lag Time—Slows the response of the digitalvalve controller. A
DVC6000 SISSeptember 20134-14 Reference Voltage Shutdown—When enabled,the instrument shuts down whenever there is a failureassociated with the intern
Detailed SetupSeptember 20134-15ALERT IS CLEAREDALERT IS SETTRAVEL ALERTHIGH POINTTRAVEL ALERTDEADBANDA6532/ILFigure 4-2. Travel Alert DeadbandTravel
DVC6000 SISvvFIELDVUE DVC6000 SIS Digital Valve ControllerTHE FIELDVUE DVC6000 SIS DIGITAL VALVE CONTROLLER IS A CORE COMPONENT OF THE PLANTWEBtDIGITA
DVC6000 SISSeptember 20134-16Deadband ReferenceDeadband (+/− 5%)Deadband exceeded,new Reference PointestablishedPointThis amount of change isadded to
Detailed SetupSeptember 20134-17Alert Record (1-2-3-7)To be recorded, an alert must both be enabled forreporting, and the group in which it resides mu
DVC6000 SISSeptember 20134-18active. The Dead Zone is configurable from 0% to 2%,corresponding to a symmetric window from 0% to+/−2% around the Primar
Detailed SetupSeptember 20134-19ABSingle-Acting Direct (Relay C)Instrument goes to zero air out-put at port A.Failure direction per actuator fail mode
DVC6000 SISSeptember 20134-20Figure 4-7. Feedback Connection for Typical Sliding-StemActuator (Up to 4 inch Travel)ACTUATORSTEMTRAVEL SENSOR SHAFTFEED
Detailed SetupSeptember 20134-21ACTUAL TRACE FROM TEST (TYPICAL)ACTUAL TRACE FROM TEST (TYPICAL)ACTUAL TRACE FROM TEST (TYPICAL)Figure 4-9. Time Serie
DVC6000 SISSeptember 20134-22Manual SIS / Partial Stroke ParameterConfigurationNoteIn order to manually set the partialstroke pressure limit with the
Detailed SetupSeptember 20134-23Table 4-10. Estimates for Partial Stroke Pressure LimitsActuator Style Relay TypeZero PowerConditionPST Starting Point
DVC6000 SISSeptember 20134-244
CalibrationSeptember 20135-15-5Section 5 Calibration Calibration Overview 5-2...Travel Calibration 5-3
Introduction and SpecificationsSeptember 20131-11-1Section 1 Introduction and SpecificationsScope of Manual 1-2...
DVC6000 SISSeptember 20135-2Calibration Overview When a DVC6000 SIS digital valve controller isordered as part of a control valve assembly, thefactory
CalibrationSeptember 20135-3Travel Calibration There are two procedures available for calibratingtravel: Auto Calibration Manual CalibrationAuto Cal
DVC6000 SISSeptember 20135-4approximately 10.0°, 1.0°, and 0.1°, respectively, tothe rotation of the feedback arm.If another adjustment is required, r
CalibrationSeptember 20135-5Note0% Travel = Valve Closed100% Travel = Valve Open1. Adjust the input current until the valve is nearmid-travel. Press
DVC6000 SISSeptember 20135-68. From the adjustment menu, select the direction andsize of change required to set the travel to 0%.Selecting large, med
CalibrationSeptember 20135-7large, medium, and small adjustments causeschanges of approximately 3.0 psi/0.207 bar/20.7 kPa,0.30 psi/0.0207 bar/2.07 kP
DVC6000 SISSeptember 20135-8Table 5-2. Travel Sensor CountsDigital Valve Controller Travel Sensor CountsDVC6010 SIS / DVC6015 700 ±200DVC6020 SIS / DV
CalibrationSeptember 20135-9Figure 5-4. FIELDVUE DVC6020 SIS Digital Valve Controller Mounted on a Fisher 1052 Size 33 ActuatorMOUNTINGADAPTER(KEY 117
DVC6000 SISSeptember 20135-10Analog Input (1-3-2-3) NoteAnalog Input Calibration is onlyavailable in 4-wire systems(point-to-point operation).To cal
CalibrationSeptember 20135-11Figure 5-5. Location of Relay Adjustment (Shroud Removed for Clarity)ADJUSTMENT DISCFOR DOUBLE-ACTING RELAYS:ROTATE ADJUS