Emerson Autochangeover Controllers AC8 Uživatelský manuál

Procházejte online nebo si stáhněte Uživatelský manuál pro Počítačové příslušenství Emerson Autochangeover Controllers AC8. Emerson Autochangeover Controllers AC8 User Manual Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 128
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků

Shrnutí obsahu

Strany 1 - USER MANUAL

SITE MONITORING AND SERVICESAC8USER MANUAL

Strany 2

Introduction21.5 Outside Enclosure OverviewThe AC8’s controller board comes in an enclosure that is 2-3/4" deep and has a built-in liquid crystal

Strany 3 - TABLE OF CONTENTS

Silence Alarm & Back Up Log Files (Service Terminal Interface only)92A.5 SILENCE ALARM & BACK UP LOG FILES (SERVICE TERMINAL INTERFACE ONLY)Th

Strany 4

Silence Alarm & Back Up Log Files (Service Terminal Interface only)93A.5.2 Back Up Log Files (Service Terminal Interface only) For details on this

Strany 5 - 8.0 SPECIFICATIONS

Silence Alarm & Back Up Log Files (Service Terminal Interface only)94Back Up Trend Log FilesBackup Log Files - Trend Log FilesBACKUP LOG FILESBack

Strany 6

Setup Menu95A.6 SETUP MENUThe Setup menu allows the user to configure the AC8—setting up inputs and outputs and an input/output matrix to trigger acti

Strany 7

Setup Menu96Setup Menu This section presents Service Terminal Interface screens for each of the following:* Setup System Information features are:• Ch

Strany 8

Setup Menu97A.6.1 Setup InputsFor details on this feature, see 7.3 - Setup System - Setup Inputs.A.6.2 Setup Common AlarmFor details on this feature,

Strany 9 - 1.0 INTRODUCTION

Setup Menu98A.6.3 Setup SensorFor details on this feature, see 7.5 - Setup System - Setup Sensor.Setup SensorSETUP SENSORSetup for analoginput pointsS

Strany 10 - ALL CIRCUITS;

Setup Menu99A.6.4 Setup ZonesFor details on this feature, see 7.6 - Setup System - Setup Zones.A.6.5 Setup OutputFor details on this feature, see 7.7

Strany 11 - 1.6 Typical Configuration

Setup Menu100A.6.6 Setup Modem & PagersFor details on this topic, see 7.8 - Setup System - Setup Modem & Pagers.Pager SetupFor details on this

Strany 12 - PFM5 PFM2

Setup Menu101Modem SetupFor details on this feature, see 7.8.1 - Modem Setup - Initialization String and 7.8.2 - Modem Setup - Additional Features (Se

Strany 13

Introduction31.6 Typical ConfigurationFigure 3 shows an example of external devices connected to the AC8’s controller board. Up to eight devices may b

Strany 14 - 1.8 LED Indicators

Setup Menu102A.6.7 Setup System InfoThis section presents Service Terminal Interface screens for choices 1 through 9 in the Setup System Information m

Strany 15 - 1.9 Typical Sequence

Setup Menu103Set Date & Time/Automatic Daylight Saving TimeFor details on this feature, see 7.9.2 - Change Date & Time/Automatic Daylight Savi

Strany 16 - 2.0 INSTALLATION

Setup Menu104Backup and Upload Configuration File (Service Terminal Interface only)For details on this feature, see 7.9.5 - Backup and Upload Configur

Strany 17 - 2.2 Surface-Mounting the AC8

Setup Menu105Setup Service Phone Number For details on this feature, see 7.9.6 - Setup Serv Ph Num - Enter Phone Number and 7.9.7 - Setup Serv Ph Num

Strany 18 - 2.3 Flush-Mounting the AC8

Setup Menu106Firmware Update (Service Terminal Interface only)For details on this feature, see 7.9.9 - Perform Firmware Update (Service Terminal Inter

Strany 19 - 2.4 Connect Power to the AC8

Setup Menu107A.6.8 Setup OperationFor details on this feature, see 7.10 - Setup Operation.Auto SequencingFor details on this feature, see 7.10.1 - Tur

Strany 20 - 2.4.3 Turning On the AC8

Setup Menu108Standby TestingFor details on this feature, see 7.10.2 - Turn Standby Testing On or Off.Setup Operation - Standby TestingSETUP OPERATION

Strany 21 - 3.0 WIRING AND CONNECTIONS

Setup Menu109Failed StandbyFor details on this feature, see 7.10.3 - Specify Failed Standby Response.Setup Operation - Failed StandbySETUP OPERATION B

Strany 22 - EPOP INPUT

Setup Menu110Hold DelayFor details on this feature, see 7.10.4 - Specify Hold Delay Time.Setup Operation - Hold DelaySETUP OPERATION BY ZONESelect the

Strany 23

Setup Menu111Restart DelayFor details on this feature, see 7.10.5 - Specify Restart Time.Setup Operation - Restart DelaySETUP OPERATION BY ZONESelect

Strany 24 - 3.2.6 Setting the EPOP Jumper

Introduction41.7 Controller Board OverviewThe AC8’s controller board has connectors for eight digital inputs, four analog inputs, eight digital output

Strany 25 - 3.3 Connecting Analog Inputs

Setup Menu112StagingFor details on this feature, see 7.10.6 - Specify Staging.Setup Operation - StagingSETUP OPERATION BY ZONESelect the zone for whic

Strany 26 - 3.6.2 Phone Line Connector

Setup Menu113A.6.9 Override Output For details on this feature, see 7.12 - Override Output.Override OutputOVERRIDE OUTPUTManually overridean outputSel

Strany 27 - 4.0 OVERVIEW OF MENUS

Setup Menu114A.6.10 Clear Alarms & LogsFor details on this topic, see 7.13 - Clear Alarms & Logs.Clear Active AlarmsFor details on this featur

Strany 28 - 4.3 LCD Menu Overview

Setup Menu115Clear the Event Log For details on this feature, see 7.13.3 - Clear the Event Log.Clear the Trend LogsFor details on this feature, see 7.

Strany 29 - 5.0 VIEW STATUS OPTIONS

Setup Menu116A.6.11 Setup I/O MatrixFor details on this feature, see 7.11 - Setup System - Setup I/O Matrix.Setup I-O Matrix - Map Input to Control Re

Strany 30 - 5.1 View Active Alarms

Setup Menu117APPENDIX B- DEFAULT SETTINGS QUICK REFERENCE GUIDEThis appendix provides a quick reference to default settings for the AC8. These setting

Strany 31 - 5.2 View Alarm Log

Setup Menu118Table 36 AC8 - other default settingsDEFAULT SETTINGS - operation features (FROM Table 28)Feature Default Other OptionsAUTO SEQUENCING OF

Strany 33 - 5.4 View Trend Log

The Company Behind the ProductsWith over a million installations around the globe,Liebert is the world leader in computer protectionsystems. Since its

Strany 34 - 5.5 View Input Status

Introduction5J - Digital output connectorsEach of the eight output connections is a two-state point: ON/OFF (energized/de-energized).An example of a f

Strany 35 - 5.6 View Output Status

Introduction61.8 LED IndicatorsThe AC8’s controller board has LED indicators that show the status of inputs, outputs and the com-mon alarm, as well as

Strany 36 - 5.7 View Pager Numbers

Introduction71.9 Typical SequenceFigure 4 shows a typical sequence of how the AC8 functions after detecting a change in a monitored device. Many respo

Strany 37 - 5.8 View Operation

Installation82.0 INSTALLATIONThis section provides instructions for installing, mounting and connecting power to the AC8.2.1 Installation Consideratio

Strany 38 - 5.9 View Control Status

Installation92.2 Surface-Mounting the AC8After determining where to place the unit, check to ensure that you have all the hardware required to install

Strany 39

Installation102.3 Flush-Mounting the AC8The AC8 may be flush-mounted according to company practices—either with screws through the sides of the panel

Strany 40

Installation112.4 Connect Power to the AC8The AC8 must be supplied with 115VAC or 230VAC; the power supplied must match the rating of the unit’s Trans

Strany 42 - 7.1 Login

Installation1224 VAC Output Power ConnectionsTo connect to the 24VAC outputs:1. Install electrical wiring from device requiring 24VAC power to the Tra

Strany 43 - ↑↓=SELECT ↵=NEXT/END

Wiring and Connections133.0 WIRING AND CONNECTIONS3.1 Wiring SpecificationsInput and output connections to the AC8 may be made in any order—it is not

Strany 44 - 7.2 Setup System - Overview

Wiring and Connections143.2 Connecting Digital Inputs and Digital OutputsThe digital inputs, digital outputs and control relay outputs are found on th

Strany 45

Wiring and Connections153.2.2 Connecting Digital OutputsTo connect a digital output:1. Turn OFF electrical power to the AC8.2. If necessary, remove a

Strany 46 - 7.3.5 Set Up Delay Time

Wiring and Connections163.2.4 Connecting Control Relay OutputsTo connect a control relay output:1. Turn OFF electrical power to the AC8.2. If necessar

Strany 47

Wiring and Connections173.3 Connecting Analog InputsThe analog input connector blocks are at the bottom center of the AC8 printed circuit board, as sh

Strany 48

Wiring and Connections183.4 Connecting Common Alarm OutputsThe common alarm relay, found in the top right corner of the AC8, permits the user to conne

Strany 49 - 7.5.3 Change Units Label

Overview of Menus194.0 OVERVIEW OF MENUSThere are two ways to access the AC8: the LCD on the front of the enclosure and the Service Terminal Interface

Strany 50 - 7.5.6 Change Offset Value

Overview of Menus204.1 Opening Screen OverviewThe AC8 displays the Opening Screen at startup, as shown in Figure 8.• If any alarms are active, the Cur

Strany 51

View Status Options215.0 VIEW STATUS OPTIONSThe View Status menu allows any user to view currently active alarms, monitoring data stored in the alarm,

Strany 52 - 7.5.10 Change High Setpoint

iTABLE OF CONTENTS1.0 INTRODUCTION1.1 Methods of Viewing and Configuring the AC8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strany 53 - 7.5.11 Set Up Delay Time

View Status Options225.1 View Active AlarmsThe Active Alarm screen displays all alarms that are occurring, up to a maximum of 22.A Current Alarm scree

Strany 54 - 7.6.1 Set Up a Zone

View Status Options235.2 View Alarm LogThe Alarm Log contains up to 99 records of alarms that have occurred. Records are added to this log as alarms o

Strany 55

View Status Options245.3 View Event LogIn addition to alarms, the AC8 tracks other changes in the Event Log to assist users with verifying operational

Strany 56

View Status Options255.4 View Trend LogThe AC8 takes readings of configured analog input sensors at regular intervals and stores them in four separate

Strany 57 - Configuring the Modem

View Status Options265.5 View Input StatusThe Input Status option allows you to view the current status of all inputs: the four analog sensor inputs a

Strany 58

View Status Options275.6 View Output StatusThe Output Status option allows you to view the current status of all eight outputs. To view the Output Sta

Strany 59

View Status Options285.7 View Pager NumbersThe AC8 may be set up to dial pager numbers when an alarm is detected. Up to four pagers may be configured,

Strany 60

View Status Options295.8 View OperationThe Operation option allows you to view the current settings for Auto Sequencing, Standby Testing and Staging i

Strany 61

View Status Options305.9 View Control StatusThe Control Status option allows you to view the current status of the two control relays. To view the Con

Strany 62

Silence Alarm & Backup Log Files (Service Terminal Interface)316.0 SILENCE ALARM & BACKUP LOG FILES (SERVICE TERMINAL INTERFACE)This section d

Strany 63

ii5.0 VIEW STATUS OPTIONS5.1 View Active Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strany 64

Silence Alarm & Backup Log Files (Service Terminal Interface)326.2 Back Up Log Files (Service Terminal Interface only)The AC8 maintains three type

Strany 65

Silence Alarm & Backup Log Files (Service Terminal Interface)335. At the top of the HyperTerminal window, shown below, click on Transfer, then on

Strany 66 - Change the Password

System and Control Options347.0 SYSTEM AND CONTROL OPTIONSThe System and Control menu allows you to configure the AC8—setting up inputs and outputs an

Strany 67 - 7.9.4 Connect Battery

System and Control Options35Figure 10 Menu overview - System and Control menuOpening ScreenLIEBERT AC8DD-MON-YY HR:MM:SSVX.XXX.XPRESS ↵=STATUS/SETUPMa

Strany 68

System and Control Options367.2 Setup System - OverviewThe Setup System screen displays seven options that allow you to configure input and output dev

Strany 69

System and Control Options377.3.1 Change Label (Name of Input)Each input has a default label (Device_1, Device_2, etc.) that you may change to a more

Strany 70

System and Control Options387.3.4 Set Up Alarmable Inputs in Latched or Unlatched ModeAlarmable input points may be set up in Latched mode (Y), which

Strany 71

System and Control Options397.4 Setup System - Setup Common AlarmThe audible alarm sounds after the AC8 detects an alarm condition in any input that h

Strany 72

System and Control Options407.5 Setup System - Setup SensorThe AC8 has four analog sensor input points that may be configured individually. The panel

Strany 73 - 7.9.8 Factory Defaults

System and Control Options417.5.1 Identify the Sensor as ConnectedTo make use of an analog sensor, you must specify it as Connected (Y). By default, a

Strany 74

iii7.6 Setup System - Setup Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 467.6.1 Set Up

Strany 75

System and Control Options427.5.4 Change 4 mA ValueFor the 4 mA value, enter the smallest value for the range of the sen-sor—for example, 50°F for a t

Strany 76 - 7.10 Setup Operation

System and Control Options437.5.7 Define Sensor as Alarmable or EventEach sensor may be defined as Alarmable (AL) or as an Event (EV).• For a sensor d

Strany 77

System and Control Options447.5.9 Change Low SetpointWhen the sensor detects a condition below the Low Setpoint value, an alarm or event will occur, d

Strany 78

System and Control Options457.5.11 Set Up Delay TimeEach sensor may be set up with a specified time delay between the triggering of a high or low setp

Strany 79 - 7.10.5 Specify Restart Time

System and Control Options467.6 Setup System - Setup ZonesThe AC8 has four zones that may be used to define different areas—rooms or sections of a roo

Strany 80 - 7.10.6 Specify Staging

System and Control Options477.7 Setup System - Setup OutputsThe AC8 has eight outputs that may be configured individually. These outputs correspond to

Strany 81

System and Control Options487.7.2 Define Operating or Standby ModeEach output may be defined as Operating (OP), Standby (ST), or Not Used (NU). This s

Strany 82 - Map Sensor to Control Relay

System and Control Options497.8 Setup System - Setup Modem & PagersTo use the modem and pager features, be sure to connect the phone line connecto

Strany 83 - 7.12 Override Output

System and Control Options50International Dialing7. To enable international dialing involving countries that do not support country code B5 (see Table

Strany 84 - 7.13 Clear Alarms & Logs

System and Control Options517.8.2 Modem Setup - Additional Features (Service Terminal Interface only)The Service Terminal Interface offers four additi

Strany 85 - 7.13.4 Clear the Trend Logs

ivAPPENDIX A-SERVICE TERMINAL INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79A.1 Comparison of Functions: LC

Strany 86

System and Control Options52Enable Modem Diagnostic MessagesEnabling modem diagnostics will provide the following additional information about the mod

Strany 87

System and Control Options537.8.3 Pager Setup - Pager Number and PINThe AC8 may be configured to dial numeric or alphanumeric pagers when an alarm is

Strany 88 - A.2.2 Create a Connection

System and Control Options54Enter a Pager Number• From the Setup Pager Menu, choose Setup Pager Number for the selected pager—Setup Pager 1 Number in

Strany 89 - COM1 Port Setup

System and Control Options557.8.4 Pager Setup - Communications Check (Service Terminal Interface only)The Service Terminal Interface offers two additi

Strany 90 - ASCII Setup

System and Control Options56Enable Communications CheckEnabling this function permits a daily communications test between the AC8 and the selected pag

Strany 91

System and Control Options577.9 Setup System - Setup System InfoThe Setup System Info options allow users to:• Change Password—used for access to syst

Strany 92 - A.3 OVERVIEW OF MENUS

System and Control Options587.9.1 Change PasswordA password is required to access the AC8’s system and control options, as described in 7.1 - Login. T

Strany 93 - A.4 VIEW STATUS MENUS

System and Control Options597.9.3 Setup Site IDYou may enter a Site ID to identify the AC8’s location, using a name that may consist of up to 40 chara

Strany 94 - A.4.2 View Alarm Log

System and Control Options607.9.5 Backup and Upload Configuration File (Service Terminal Interface only)This operation may be performed only through t

Strany 95 - A.4.3 View Event Log

System and Control Options61Back Up the Configuration File8. At the prompt to Initiate a Backup of Configuration File, enter Y (Yes - begin) or N (No

Strany 96 - A.4.4 View Trend Log

vFIGURESFigure 1 AC8 enclosure—external features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strany 97 - A.4.6 View Output Status

System and Control Options62Upload the Configuration File13. At the prompt to Initiate an Upload of Configuration File, enter Y (Yes - begin) or N (No

Strany 98 - A.4.7 View Pager Numbers

System and Control Options637.9.6 Setup Serv Ph Num - Enter Phone NumberThe Service Phone Number (Serv Ph Num) is used for remote monitoring by Lieber

Strany 99 - A.4.9 View Control Status

System and Control Options647.9.7 Setup Serv Ph Num - Communications Check (Service Terminal Interface only)The Service Terminal Interface offers two

Strany 100 - Main Menu

System and Control Options657.9.8 Factory DefaultsAt any time, you may restore all default values for settings in the AC8 as it was shipped.The passwo

Strany 101 - Back Up Event Log File

System and Control Options662. The firmware update is a two-step process—this step describes how to upload the file prog###.s19 (where ### is a number

Strany 102 - Back Up Trend Log Files

System and Control Options677.9.10 Initiate Remote Alarm Test (Service Terminal Interface only)The service phone number is used for remote monitoring

Strany 103 - A.6 SETUP MENU

System and Control Options687.10 Setup OperationThe AC8’s operation features allow you to set up a rotation sequence to alternate which devices are op

Strany 104 - Setup Menu

System and Control Options697.10.1 Turn Automatic Sequencing On or OffUse automatic sequencing to set up a schedule for rotation of redundant devices.

Strany 105 - A.6.2 Setup Common Alarm

System and Control Options707.10.2 Turn Standby Testing On or OffStandby testing permits scheduling an automatic operational check of devices in Stand

Strany 106 - A.6.3 Setup Sensor

System and Control Options717.10.4 Specify Hold Delay TimeAfter an output changes state, the hold delay timer directs the AC8 to ignore all inputs in

Strany 108 - Pager Setup

System and Control Options727.10.6 Specify StagingStaging allows a standby device to be turned On when a sensor detects a monitored point reaching a s

Strany 109 - Modem Setup

System and Control Options737.11 Setup System - Setup I/O MatrixThe Setup I/O Matrix menu allows you to configure the AC8’s digital and analog inputs

Strany 110 - Change Password

System and Control Options747.11.2 Set Up Mapping for an Analog Sensor Input• Use the arrows ↑↓ to choose Map Sensor To Relay from the Map Input/Senso

Strany 111 - Connect Battery

System and Control Options757.12 Override OutputThe Override Output feature allows you to manually change the state of any digital output to ON or OFF

Strany 112

System and Control Options767.13 Clear Alarms & LogsThe Clear Alarms & Logs menu allows you to clear active alarms or delete all records from

Strany 113 - Factory Defaults

System and Control Options777.13.3 Clear the Event LogThe event log contains up to 99 records of events detected by the AC8. You may want to clear the

Strany 114

Specifications788.0 SPECIFICATIONS8.1 AC8 SpecificationsPowerRequirementsTransformer ModuleNOTE115VACUML11500230VACUML23000If the equipment isused in

Strany 115 - Auto Sequencing

Comparison of Functions: LCD and Service Terminal Interface79APPENDIX A- SERVICE TERMINAL INTERFACEThe Service Terminal Interface allows access to all

Strany 116 - Standby Testing

Connecting to the Service Terminal Interface80A.2 CONNECTING TO THE SERVICE TERMINAL INTERFACEThis section describes how to set up and connect to the

Strany 117 - Failed Standby

Connecting to the Service Terminal Interface815. In the Connect To window, shown below, select the appropriate connection method from the Connect Usin

Strany 118 - Hold Delay

Introduction11.0 INTRODUCTIONThe Liebert AC8 is ideal for coordinated control of systems with redundant equipment, such as multiple environmental unit

Strany 119 - Restart Delay

Connecting to the Service Terminal Interface82A.2.4 Set Up the Connection’s PropertiesThe following steps are needed for both direct and remote connec

Strany 120 - Setup Operation - Staging

Connecting to the Service Terminal Interface83A.2.5 Connect to the Service Terminal InterfaceAfter creating and setting up a connection, use a communi

Strany 121 - A.6.9 Override Output

Overview of Menus84A.3 OVERVIEW OF MENUSThe Main Menu offers choices for viewing the status of the AC8, silencing the audible alarm and backing up the

Strany 122 - Clear the Alarm Log

View Status Menus85A.4 VIEW STATUS MENUS The View Status menu allows any user to view currently active alarms, monitoring data stored in the alarm, ev

Strany 123 - Clear the Trend Logs

View Status Menus86A.4.2 View Alarm LogFor details on this feature, see 5.2 - View Alarm Log.View Alarm LogALARM LOGAlarm historySENSOR_2 80.0 DEGH

Strany 124 - A.6.11 Setup I/O Matrix

View Status Menus87A.4.3 View Event LogFor details on this feature, see 5.3 - View Event Log.View Event LogEVENT LOGEvent historyPAGERUNSUCCESSFUL PAG

Strany 125 - ) indicating a problem

View Status Menus88A.4.4 View Trend LogFor details on this feature, see 5.4 - View Trend Log.View Trend LogTREND LOGTrend historyfor each sensorSelect

Strany 126

View Status Menus89A.4.5 View Input StatusFor details on this feature, see 5.5 - View Input Status.A.4.6 View Output StatusFor details on this feature

Strany 127

View Status Menus90A.4.7 View Pager NumbersFor details on this feature, see 5.7 - View Pager Numbers.View Pager NumbersPAGER & PIN NUMBERSNumbers

Strany 128

View Status Menus91A.4.8 View OperationFor details on this feature, see 5.8 - View Operation.A.4.9 View Control StatusFor details on this feature, see

Komentáře k této Příručce

Žádné komentáře