Installation Drawings 41
Figure 23 Control Wiring for Remote Source Selection Option
STATICSWITCH2/CONTROLWIRE/PS213007-01(C)
6/9/03
PS213007
CONTROL WIRING
REMOTE SOURCE SELECTION OPTION
STATIC TRANSFER SWITCH 2
REMOTE SOURCE SELECTION
DATE
FILE NAME:
COLUMBUS, OHIO 43229
1050 DEARBORN DRIVE,
REV. NO.
DWG. NO.
V CARMONA
REF. DWG.
CHK BY
DRAWN BY
SOURCE 1
PREFERRED
213456
SOURCE 2
PREFERRED
SEE NOTE 1
NOTES:
5. ALL WIRING MUST BE IN ACCORDANCE WITH NATIONAL
DIAGRAM FOR LOCATION OF REMOTE SOURCE SELECTION OPT.
4. REFER TO STATIC TRANSFER SWITCH CONTROL CONNECTION
SEPARATE FROM POWER WIRING. CONTROL WIRING RUNS
3. ALL CONTROL WIRING (BY OTHERS) MUST BE RUN
SHOULD NOT BE COMBINED IN THE SAME CONDUIT.
1. CUSTOMER PROVIDED NORMALLY OPEN DRY CONTACTS.
AND LOCAL ELECTRICAL CODES.
S1 GND S2 GND
1
RATING 10mA AT 30VDC.
TB50
2. MAXIMUM CABLE LENGTH 500 FT. (152 METERS) WITH
#16AWG 300V MINIMUM, FLEXIBLE STRANDED CABLE.