Precision Cooling
For Business-Critical Continuity™
Liebert
®
iCOM
®
User Manual - Intelligent Communications & Monitoring for Liebert Challenger 3000
, Liebert
Challenger ITR
, Liebert CW
and Liebert DS
Zobrazit stránku 0
1 2 3 4 5 6 ... 99 100

Shrnutí obsahu

Strany 1 - and Liebert DS

Precision CoolingFor Business-Critical Continuity™Liebert® iCOM®User Manual - Intelligent Communications & Monitoring for Liebert Challenger 3000™

Strany 2 -

Liebert iCOM Display Components and Functions4Figure 3 Status menu, large display, graphical viewFigure 4 Liebert iCOM default screen symbolsUNIT 111/

Strany 3 - TABLE OF CONTENTS

Ensuring The High AvailabilityOf Mission-Critical Data And Applications.Emerson Network Power, the global leader in enabling business-criticalcontinui

Strany 4

Liebert iCOM Display Components and Functions52.1 Navigating Through the Liebert iCOM MenusLiebert iCOM shows icons and text for monitoring and contro

Strany 5

Liebert iCOM Display Components and Functions6Accessing Submenus on Small DisplaysWhile viewing the menu you wish to access (User, Service or Advanced

Strany 6

Liebert iCOM Display Components and Functions7Figure 6 Entering a passwordFigure 7 Menu tree—Large display, stand-aloneSETPOINTSto change parameterto

Strany 7 - 1.0 INTRODUCTION

Liebert iCOM Display Components and Functions82.1.4 Viewing Multiple Units with a Networked Large DisplayWhen you first wake up the control, press the

Strany 8

Liebert iCOM Display Components and Functions9Figure 9 User menu iconsTable 2 User menu iconsIcon NameDescriptionAvailable On DisplaySetpointsView and

Strany 9

Liebert iCOM Display Components and Functions10Figure 10 Service menu iconsSleep ModeAllows setback settings for non-peak operationSmall & LargeSe

Strany 10

Liebert iCOM Display Components and Functions11Sensor Calibration/SetupAllows calibration of sensors Small & largeSystem/Network SetupAllows setup

Strany 11 - 2.1.2 Accessing Submenus

Operation123.0 OPERATIONThe Liebert iCOM display provides viewing, trending and configuration capability for Liebert cooling units. All unit settings

Strany 12 - 2.1.3 Entering a Password

Operation13AutorestartWhen there is a loss of power to the cooling unit and power comes back, the unit will return to its pre-vious operating status—o

Strany 14

Operation14Chilled Water Units with Variable Fan Speed—EC or Variable Frequency DrivesVSD Fan Speed parameter can be found in the Service Menu / Setpo

Strany 15 - Table 2 User menu icons

Operation153.1.2 General Compressor RequirementsLow-Pressure Time DelayWhen the compressor starts, the low-pressure input is ignored for a selected pe

Strany 16 - Table 3 Service menu icons

Operation16Digital Scroll High TemperatureA protective maximum operating compressor temperature limit is imposed on units with digital scroll compress

Strany 17

Operation17 When Auto BV Control is selected, the motorized ball valve functions as it would be during normal system operation.When Manual BV Control

Strany 18 - 3.0 OPERATION

Operation183.2 Temperature Control—Single Source Cooling (No Extra Cooling Coil)3.2.1 Temperature Proportional Band The control uses the temperature p

Strany 19 - Loss of Power Alarm

Operation193.2.2 Compressor ControlDepending on its type, a Liebert Precision Cooling unit may have one or two compressors with or without unloaders o

Strany 20 - Operation

Operation20Two Compressors With Unloaders—Four-StepThe first two-step compressor is started unloaded at 33% calculated output from the temperature pro

Strany 21 - High Pressure Alarm

Operation21On single and dual digital scroll compressor systems, the first compressor is started at 25% calculated output from the temperature proport

Strany 22

Operation223.2.3 Chilled Water ControlThe chilled water control valve is adjusted proportionally as the temperature control varies the requirement for

Strany 23

Operation23Chilled water units that contain a motorized ball valve(s) are connected to the control by an analog output. The analog output is driven pr

Strany 24

iTABLE OF CONTENTS1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strany 25 - Compressor Proportional Bands

Operation24Figure 20 Second cooling source and two-step compressorized coolingMinimum Chilled Water Temperature—This feature permits the user to selec

Strany 26

Operation253.4 Temperature Control—ReheatIf the room air temperature becomes too cold, the control will call for heating. Heating mode is con-trolled

Strany 27

Operation26capacity is provided at 0% calculated output from the Temperature Proportional Band. As the call for cooling increases from 0% to 100%, the

Strany 28 - 3.2.3 Chilled Water Control

Operation27Figure 23 Two single-step compressors with SCR reheat set to Standard mode3.5 Humidity ControlThe control uses the humidity proportional ba

Strany 29

Operation28When the return air humidity reaches the end of the proportional band, either 100% or -100%, full dehumidification or full humidification c

Strany 30 - Dual Cooling Source

Operation293.5.2 DehumidificationThe Dehumidification Enable parameter (Service Menu, Options Setup) allows for enabling/disabling the dehumidificatio

Strany 31 - 3.4.2 SCR Reheat

Operation30Reheat During DehumidificationHot gas reheat or hot water reheat will start as described in 3.4 - Temperature Control—Reheat, when the temp

Strany 32

Operation31is programmed into the control. These rules simulate the actions that a human operator would take if manually controlling the system. This

Strany 33

Operation32Figure 25 Placing temperature and temperature/humidity sensorsTemperature Sensor5 to 15feet(1.5 to 4.5m)Internal Temperature and Humidity

Strany 34 - Infrared Humidifier

Operation333.7 Supply Control3.7.1 Supply AirThe Supply Air sensor can be used to control, limit or reference the discharge air temperature of the coo

Strany 35 - Dehumidification Low Limit

ii4.0 TEAMWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .414.1 Teamwork Mo

Strany 36 - 3.6 Control Types

Operation343.8 Event Types and PropertiesLiebert iCOM events are used to inform the user of cooling unit operational status. All events are recorded i

Strany 37

Operation35Table 7 Possible event settings—some events not available in all unitsEventInternal Delay(Before Action Occurs)Default Delay / Selectable(B

Strany 38

Operation363.8.1 High- and Low-Temperature and Humidity EventsHigh- and low-temperature and humidity alarms can be set for both the internal and optio

Strany 39 - 3.7 Supply Control

Operation373.8.3 Liebert iCOM-DOThe Liebert iCOM-DO is an optional discrete output relay card that can be connected to the Liebert iCOM controls that

Strany 40

Operation383.8.4 Possible Event NotificationsTable 10 lists examples of alarms and warnings that can be configured for a cooling unit. When any of the

Strany 41

Operation393.9.1 Calculation of Next Maintenance and DiagnosticsIf the unit includes any of the following components, they are included in the calcula

Strany 42 - 3.8.2 User Inputs

Operation40Fans / Heaters / Humidifier Settings and Diagnostics• Number of starts and Working hours are counted separately since the last maintenance.

Strany 43 - 3.8.3 Liebert iCOM-DO

Teamwork414.0 TEAMWORKUnit-2-Unit (U2U) communications via a private network will allow the following functions to be placed into operation when the r

Strany 44

Teamwork42The number of available units is calculated like:• In non-standby configuration: all units with fan on• In typical standby function (no casc

Strany 45 - Calculating Unit Wellness

Teamwork434.1.4 Teamwork Mode 2Teamwork Mode 2 is designed to prevent units within a group from working against each other or “fighting.” It is best a

Strany 46

iiiFigure 27 Standby unit layout example—10 Precision Cooling units in room. . . . . . . . . . . . . . . . . . . . . . . . 44Figure 28 Connecting two

Strany 47 - 4.0 TEAMWORK

Installing a Liebert iCOM Unit-to-Unit Network445.0 INSTALLING A LIEBERT ICOM UNIT-TO-UNIT NETWORKConnecting multiple Liebert iCOM-controlled cooling

Strany 48 - Teamwork

Installing a Liebert iCOM Unit-to-Unit Network455.2 U2U Hardware: Cables and Network SwitchPlan wiring runs for U2U communication when designing the l

Strany 49 - Standby and Cascade

Installing a Liebert iCOM Unit-to-Unit Network465.3 Wiring for Unit-to-Unit Communications—U2UCooling units come from the factory-wired for stand-alon

Strany 50

Installing a Liebert iCOM Unit-to-Unit Network47Large DisplaysA network switch is required to enable Ethernet communication on one or more cooling uni

Strany 51

Installing a Liebert iCOM Unit-to-Unit Network48Wall-Mount Large DisplayOnly large displays can be used for remotely monitoring and controlling coolin

Strany 52 - Small Displays

Installing a Liebert iCOM Unit-to-Unit Network49Figure 31 Wiring a small display for U2U network operationStandard SmallGraphics Display(Rear View)Lie

Strany 53 - Large Displays

Installing a Liebert iCOM Unit-to-Unit Network50Figure 32 Wiring a large display for U2U network operationLiebert vNSAThe Liebert vNSA is designed to

Strany 54 - Wall-Mount Large Display

Installing a Liebert iCOM Unit-to-Unit Network51Figure 33 Liebert vNSA with optional remote large displayTable 12 Ports available for connecting Liebe

Strany 55 - I/O Board

External Communications—Building Management Systems, Liebert SiteScan®526.0 EXTERNAL COMMUNICATIONS—BUILDING MANAGEMENT SYSTEMS, LIEBERT SITESCAN®Lieb

Strany 56 - (Rear View)

User Menu Parameters537.0 USER MENU PARAMETERSUser menus report general cooling unit operations and status. The user menu password is 1490.The User me

Strany 57

ivFigure 77 Sensor calibration / setup parameters - Page 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86Figure 78

Strany 58 - SITESCAN

User Menu Parameters54Spare Part ListSpare Parts—The spare parts lists contains a detailed description and part number that can be used to order parts

Strany 59 - 7.0 USER MENU PARAMETERS

User Menu Parameters55Low Temperature Sensor A—This parameter is visible when the sensor A alarm is enabled. When enabled the low temperature alarm al

Strany 60 - View Network

User Menu Parameters56Figure 37 Sensor data screenOptional Sensor A1—When a optional reference sensor is connected to the Liebert iCOM controller area

Strany 61 - User Menu Parameters

User Menu Parameters57Figure 38 Sensor data screen - Page 2 (return only)Daily High Temperature—The daily high temperature is the highest recorded tem

Strany 62

User Menu Parameters58Figure 39 Display setup parameters screenLanguage—This parameter sets the language on the display. When this parameter is change

Strany 63 - Active Alarms

User Menu Parameters59Figure 40 Total run hours parameters screenFigure 41 Sleep mode parameters screenTOTAL RUN HOURSto change parameterto confirmto

Strany 64

Service Menu Parameters608.0 SERVICE MENU PARAMETERSService menus allow customized settings for site operations. The password for service menu parame-

Strany 65

Service Menu Parameters61Figure 43 Setpoints parameters screen - Page 1Temperature Setpoint—This parameter selects a temperature that the cooling unit

Strany 66 - 8.0 SERVICE MENU PARAMETERS

Service Menu Parameters62Figure 44 Setpoints parameters screen - Page 2Humidity Setpoint—This parameter allows the user to select a humidity that the

Strany 67

Service Menu Parameters63Figure 45 Setpoints parameters screen - Page 3Supply Sensor—This parameter selects how the supply sensor will be used by the

Strany 68

Introduction11.0 INTRODUCTIONThe Liebert iCOM® control offers the highest capabilities in unit control, communication and moni-toring of Liebert missi

Strany 69

Service Menu Parameters64Figure 46 Setpoints parameters screen - Page 4DT between Room / Outdoor Type—This feature is only used on HPM products.DT bet

Strany 70

Service Menu Parameters65Figure 47 Setpoints parameters screen - Page 5VSD Fanspeed—This parameter sets the control type for a variable fanspeed devic

Strany 71

Service Menu Parameters66Figure 48 Setpoints parameters screen - Page 6SCR Control Type—This parameter sets the control type for the SCR re-heats. If

Strany 72 - Unit Diary—Large Display Only

Service Menu Parameters67Figure 49 Standby settings / lead-lag parameters screenNumber of Standby Units—This parameter selects the number of units tha

Strany 73

Service Menu Parameters68Figure 50 Wellness basic settings screen- Page 1Maximum Frequency Per year—This parameter sets the number of expected mainten

Strany 74

Service Menu Parameters69Figure 51 Wellness motor settings parameters screen - Page 2 Figure 52 Wellness compressor 1 settings parameters screen - Pag

Strany 75

Service Menu Parameters70Figure 53 Wellness compressor 1 settings parameters - Page 4Figure 54 Wellness electric heater 1 settings parameters screen -

Strany 76

Service Menu Parameters71Figure 55 Wellness electric heater 2 settings parameters screen - Page 6Figure 56 Wellness electric heater 3 settings paramet

Strany 77

Service Menu Parameters72Figure 57 Wellness humidifier settings parameters screen - Page 8WELLNESS humidifier settings (page 8 of 8)to change paramete

Strany 78

Service Menu Parameters73Figure 58 Diagnostics / service mode parameters screen - Page 1HP 1 Alarm Code—Compressor 1 high pressure alarm code.HP 2 Ala

Strany 79

Liebert iCOM Display Components and Functions22.0 LIEBERT ICOM DISPLAY COMPONENTS AND FUNCTIONSThe small and the large display have a common key layou

Strany 80

Service Menu Parameters74Figure 59 Diagnostics / service mode parameters screen - Page 2Manual Mode—Use this setting to place the Liebert iCOM control

Strany 81

Service Menu Parameters75Figure 60 Diagnostics / service mode parameters screen - Page 3Electric Heat 1 (or HG/HW)—This will activate stage 1 of the u

Strany 82

Service Menu Parameters76Figure 61 Diagnostics / service mode parameters screen - Page 4Alarm Relay—This allows the user to activate the Liebert iCOM

Strany 83

Service Menu Parameters77Figure 62 Diagnostics / service mode parameters screen - Page 5Status Remote Shutdown—This show the status of the unit’s remo

Strany 84

Service Menu Parameters78Figure 63 Diagnostics / service mode parameters screen - Page 6Status HP1—This shows the status of the unit’s compressor 1 hi

Strany 85

Service Menu Parameters79Status DT3 (Room/Setpoint)—This indicates if the delta T between room return air temperature and unit air temperature setpoin

Strany 86

Service Menu Parameters80Figure 66 Set alarms parameters screen - Page 2Customer Input 1, 2, 3 & 4—These parameters select the device and operatio

Strany 87 - Service Menu Parameters

Service Menu Parameters81Type—This selection sets the type of action for each event listed. There are 3 different types of events (Alarm, Warning and

Strany 88

Service Menu Parameters82Figure 70 Set alarms parameters screen - Page 6Figure 71 Set alarms parameters screen - Page 7SET ALARMS (page 6 of 7)PASSWOR

Strany 89

Service Menu Parameters83Figure 72 iCOM-DO Overview and Override - Page 1Liebert iCOM-DO—This parameter shows the connection status of a Liebert iCOM-

Strany 90

Liebert iCOM Display Components and Functions3Table 1 Keyboard icons and functionsIcon Key Name FunctionOn/Off Key Controls the operational state of t

Strany 91

Service Menu Parameters84Figure 74 iCOM-DO Events Setup - Page 3Figure 75 Sensor calibration / setup parameters - Page 1Return Temperature—This parame

Strany 92

Service Menu Parameters85Digital Scroll 2 NTC—This parameter adjusts the digital scroll 1 NTC reading from the actual sen-sor to compensate for any er

Strany 93

Service Menu Parameters86Figure 77 Sensor calibration / setup parameters - Page 3Freecool Sensor PTC or NTC—This parameter currently only supports the

Strany 94

Service Menu Parameters87Configuration Safe—This parameter saves or loads configuration settings for the display that have been modified from the fact

Strany 95

Service Menu Parameters88Figure 80 System/Network setup parameters Unit- Page 1Monitoring Address—This parameter sets the address used by the Liebert

Strany 96

Service Menu Parameters89Figure 81 System/Network setup parametersUnit - Page 2Monitoring Protocol—This parameter selects the monitoring protocol. Vel

Strany 97

Service Menu Parameters90Figure 82 Options setup parameters - Page 1Compressor Sequence—This parameter changes the lead compressor when cooling is act

Strany 98

Service Menu Parameters91Figure 83 Options setup parameters - Page 2Humidification Enabled—This parameter enables or disables humidification. Infrared

Strany 99

Service Menu Parameters92Figure 84 Options setup parameters - Page 3CW Flush—This parameter selects how many hours between each chill water coil flush

Strany 100 - SL-18835_REV5_01-10

Service Menu Parameters93Table 14 Service contact info parametersFunctionRangeImperial (metric)Large Display Small DisplayPage 1 of 1Password PASSWORD