lNTRoDUCT’oN: THIS SAFRY DATA SHEm APPLIES TO INTELEGENT FIELD TRANSMllTER
(Im3000), NPE No. 11105691. THE APPARATUS IS CERTIFIED EExd IIB T6.:
ISSeP CERTIFICATE No.
THIS APPARATUS HAS BEEN DESIGNED AND MANUFACTURED TO OPERATE
SAFELY IN CERTAIN NPES OF POTENTIALLY EXPLOSIVE ATMOSPHERES. IT 1s ESSENTIAL
THAT THE EQUIPMENT IS NOT TAMPERED WITH OR DAMAGED IN ANY WAY WHICH
MIGHT LEAD TO A REDUCTION IN IT’S ABILITY TO OPERATE SAFELY IN SUCH POTENTIALLY
EXPLOSIVE ATMOSPHERES. FOR YOUR OWN SAFETY AND THE SAFETY OF OTHERS
PLEASE BRING ANY DAMAGE TO THE ATTENTION OF THE RESPONSIBLE AUTHORITY.
THIS APPARATUS HAS BEEN DESIGNED AND MANUFACmRED IN ACCORDANCE
WITH EUROPEAN STANDARDS EN50014 8c EN50018. INSTALLATION MAINTENANCE
AND REPAIR MUST BE IN ACCORDANCE. WITH THE OFFICAL “C@ES OF
PRACTICE ON THE INSTAIATION AND MAINTAINANCE OF ELEC@ICAL APPARATUS
IN POTENTIALLY EXPLOSIVE ATMOSPHERES” FOR THE COUl@Y OF INSTALLATION
(EXAMPLE: 8~5345 IN GREAT BRITAIN). ONLY APPROPR~ATLY TRAINED PERSONNEL
ARE AUTHORISED TO PERFORM ANY W0RK ON THIS EQUIPMENT. SUCH PERSONNEL IN
ADDITION TO OPERATING TO THE ABOVE MENTlONED SAFETY STANDARDS, SHOULD TAKE
NOTE OF THE FOLLOWING SAFETY ISSUES.
(1, FLAMEPROOF APPARATUS OR NON FLAMEPROOF APPARATUS.
THE ROSEMOUNT ENCODE SHEETS (PRODUCT ORDERING MATRIX) ALLOWS A CUSTOMER
TO ORDER EITHER THE HAZARDOUS AREA (FLAMEPROOF) VERSION OF THE IFT3000
OR THE NON HAZARDOUS AREA VERSION. THE HAZARDOUS AREA VERSION HAS THE
SYMBOL “EExd” ON THE APPARATUS hIAMEPLATE. THE NON HAZARDOUS AREA VERSION
DOES NOT. ENSURE THAT IF YOU HAVE RECEIVED THE NON HAZARDOUS AREA VERSION
THAT YOU DO NOT INSTALL IT IN APOTENTIALLY EXPLOSIVE ENVIRONMENT.
(2) POWER DOWN PROCEDURE:
ISOLATION OF ELECTRICAL SUPPLY: THIS PIECE OF APPARATUS IS NOT ITSELF FIT-I-ED
WITH A MEANS OF ELECTRICAL ISOLATION. CONSULT YOUR LOCAL CODES OF PRACTICE
ON THE INSTALLATION AND MAlNTAlNAhlCE OF ELECTRICAL APPARATUS IN POTENTIALLY
EXPLOSIVE ATMOSPHRES (835345 IN IBRITAIN) FOR INSTRUCTION ON THE ISOLATION OF
ELECTRICAL SUPPLY TO THE APPARATUS. FURTHER MORE THERE MUST BE “EFFECTIVE
MEASURES TO PREVENT THE RESTORATION OF SUPPLY TO THE APPARATUS WHILE THE
RISK OF EXPOSING UNPROTECTED LIVE CONDUCTORS TO AN EXPLOSIVE ATMOSPHERE
CONTlNUES”:BS5345 PAPT 1 1989 SECTION 18.
RESTORATION OF SUPPLY FOR-EL-ICAL TESTlNG: “WHERE, FOR PURPOSES OF
ELECTRICAL TESTING, IT IS ESSENTIAL ‘TO RESTORE THE SUPPLY BEFORE THE APPARATUS
IS RE-ASSEMBLED. THEN THIS WORK SHOULD BE UNDER A CONTROLLED PROCEDURE
AND THE SPECIFIC. LOCATION ASSESSED TO ENSURE THAT POTENTIALLY FLAMMABLE
GAS OR VAPOUR IS ABSENT”:BS5345 PART 1 1989 SECTION 23.
REMOVAL OF JUNCTION BOX COVER: DO NOT OPEN THE APPARATUS COVER
WHILE THE APPARTUS IS ENERGISED. WAIT 10 MINUTES AFIER DEENERGISING BEFORE
OPENING THE APPARATUS.
(3) _\dllBu\IG OF THE APPARATUS; EACH APPARATUS MUST BE WIRED AS DETAILED IN
THE APPLICABLE INSTRUCTION BULLfllN (USER MANUAL).
(4) lNsm”cnoN BULLETINS (“sER:.MAN”AL). THE APPLICABLE INSTRUCTION BULLETIN IS:
IB-106-300NFX: USED WITH IFr3000 ELECTRONICS.
THIS INSTRUCTION BULLETIN CONTAIN ESSENTIAL INFORMATION 8c MUST BE USED
WHEN WORKING ON THE APPARATUS.
(5) CABLE GLANDS:
HAWKE CABLE GLAND, wpE icG653 (BASEEFA cERnFlcATE :
BAS No. EX 85B1258”) OR AN EQUIVALENT MUST BE USED. THIS GLAND IS A
BARRIER (STOPPER) GLAND. A FEATURE OF THIS GLAND IS THAT A COMPOUND
FILLED PACKING MATERIAL (PUllY), FORMS A BARRIER BETWEEN THE INDIVIDUAL
INSULATED CONDUCTORS OF THE CABLE. THIS BARRIER ACTS TO PREVENT ENTRY
INTO THE CABLE OF THE PRODUCTS OF AN EXPLOSION WITHIN THE ENCLOSURE.
THIS GLAND IS CERTIFIED Exd IIC.