Emerson Liebert IntelliSlot Unity Communications Interface Card Servisní příručka Strana 235

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 400
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 234
Modbus RTU and Modbus TCP Protocols - Battery Monitoring Products
229 Liebert
®
IntelliSlot
®
Modbus/BACnet
3.4 Battery Monitoring Products
Table 78 Alber
®
BDSU
- Status and Coil
Data Description
Status Coil
Number
of Bits Notes / Units
Battery Entity
Battery Discharging
Battery 1 - 32
10001-10032 1 Active on Alarm
String Entity
High Ambient Temperature
String 1 - 32
10033-10064 1 Active on Alarm
Low Ambient Temperature
String 1 - 32
10065-10096 1 Active on Alarm
Low Ambient Temperature Probe Two
String 1 - 32
10097-10128 1 Active on Alarm
High Ambient Temperature Probe Two
String 1 - 32
10129-10160 1 Active on Alarm
Low Overall Voltage
String 1 - 32
10161-10192 1 Active on Alarm
High Overall Voltage
String 1 - 32
10193-10224 1 Active on Alarm
High Battery String Current
String 1 - 32
10225-10256 1 Active on Alarm
Low Battery String Float Current
String 1 - 32
10257-10288 1 Active on Alarm
High Battery String Float Current
String 1 - 32
10289-10320 1 Active on Alarm
High Battery String Ripple Current
String 1 - 32
10321-10352 1 Active on Alarm
Battery String Discharge Detected
String 1 - 32
10353-10384 1 Active on Alarm
Maximum Discharge Time Exceeded
String 1 - 32
10385-10416 1 Active on Alarm
Discharge Low Overall Voltage
String 1 - 32
10417-10448 1 Active on Alarm
Discharge Low Cell Voltage
String 1 - 32
10449-10480 1 Active on Alarm
Discharge High Battery String Current
String 1 - 32
10481-10512 1 Active on Alarm
Excessive Cell to Cell Temperature Deviation
String 1 - 32
10513-10544 1 Active on Alarm
Excessive Cell to Ambient Temperature Deviation
String 1 - 32
10545-10576 1 Active on Alarm
Thermal Runaway Detected
String 1 - 32
10577-10608 1 Active on Alarm
Battery String Equalize
String 1 - 32
10609-10640 1 Active on Alarm
Battery String Offline
String 1 - 32
10641-10672 1 Active on Alarm
Thermal Runaway Cell to Ambient Temperature Event
String 1 - 32
13233-13264 1 Active on Alarm
Thermal Runaway Cell to Cell Temperature Event
String 1 - 32
13265-13296 1 Active on Alarm
Zobrazit stránku 234
1 2 ... 230 231 232 233 234 235 236 237 238 239 240 ... 399 400

Komentáře k této Příručce

Žádné komentáře

Vivitek Projectors user manuals

Starting on H

Click on an alphabet below to scroll to the full list of models starting with that letter

Models Document Type
H1082
Specifications   Vivitek H1082 Specifications, 50 pages
H118x Series
User Manual   1. - Vivitek, 62 pages
Specifications   Vivitek H118x Series Specifications, 50 pages
H118x series
User Manual   Инструкция по эксплуатации Vivitek H118x series, 62 pages
H5080
User Manual   HOME THEATER PROJECTOR Professional [en] , 1 pages
H9080FD
User Manual   Projektor Vivitek H9080FD, 2 pages