ROC364 Instruction Manual
Rev 5/00 6-13
6.5.4 Discrete Output Channels
Equipment Required: Multimeter
Personal Computer running ROCLINK Software
Place the Discrete Output in manual mode using the ROCLINK configuration software. Set the output
status to “0” and measure the resistance across terminals B and C. A reading of 0 ohms should be
obtained. Set the output status to “1” and measure the resistance across terminals B and C. No
continuity should be indicated.
6.5.5 Pulse Input Channels
Equipment Required: Pulse Generator
Voltage Generator
Frequency Counter
Jumper wire
For both types of channels, there are two methods of testing. One method tests high-speed operation,
and the other method tests low-speed operation.
NOTE
When checking the operation of the Pulse Input channels, ensure the scan rate for
the pulse input is once every 6.5 seconds or less as set by the ROCLINK software.
To verify high-speed operation, connect a pulse generator having sufficient output to drive the channel
to terminals B and C. Connect a frequency counter across terminals B and C. Set the pulse generator
to a value equal to, or less than 10 KHz, and set the frequency counter to count pulses. Verify the count
read by the counter and the count read by the ROC are the same using the ROCLINK software.
To verify low-speed operation, alternately jumper across terminals B and C. The channel LED should
cycle on and off, and the accumulated count should increase.