CS800 Series
5
Table 5. Outlet Pressure Ranges
TYPE
OUTLET PRESSURE RANGE
COLOR CODE PART NUMBER
SPRING WIRE DIAMETER SPRING FREE LENGTH
In. w.c. mbar In. mm In. mm
CS800, CS803,
CS804, CS805
and CS806
3.5 to 6
(1)
9 to 15
(1)
Red GE30337X012 0.15 3.8 6.8 173
5.5 to 8.5 13 to 21 Black GE30338X012 0.17 4.3 6.8 173
5.5 to 8.5 13 to 21
Brown [Use with Low
Inlet (LIN) Option]
GE49043X012 0.16 4.1 8.3 211
8 to 12 20 to 30 Purple GE30339X012 0.17 4.3 7.4 188
10 to 16 25 to 40 White GE30340X012 0.18 4.6 7.4 188
14 to 30 35 to 75 Dark Green GE30341X012 0.20 5.2 7.5 191
CS820, CS823,
CS824, CS825
and CS826
1 to 2.5 psig 69 to 170 Dark Blue GE30342X012 0.25 6.4 7.5 191
1.5 to 3.5 psig 100 to 241 Orange GE46922X012 0.26 6.6 7.1 180
2.5 to 5.5 psig 170 to 380 Yellow GE30343X012 0.29 7.5 6.7 170
CS850 and
CS854
5 to 10 psig 345 to 690
Green with
White Stripe
GE30344X012 0.39 9.9 7.6 192
1. In order to achieve the complete spring range listed, in some applications it may be required to re-orient the actuator/spring case to point downward to utilize the weight of the
internal components.
Table 7. Secondary Seat™ Protection Outlet Pressures
CONTROL SPRING SPRING RANGE SETPOINT
TYPES CS805 AND CS825 TYPES CS806 AND CS826
Secondary Seat
Shut-off Pressure
(2)
Downstream Build-up
Pressure
(1)(2)(3)
Orice Size, In. / mm Orice Size, In. / mm
3/8 / 9.5 5/8 / 16 3/8 / 9.5 5/8 / 16
Color Part Number In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar
Black GE30338X012 5.5 to 8.5 13 to 21 7 17 11 27 12 30 25 62 23 57
Brown
(LIN)
GE49043X012 5.5 to 8.5 13 to 21 7 17 11 27 12 30 25 62 23 57
White GE30340X012 10 to 16 25 to 40 14 35 19 47 20 50 36 89 33 81
Dark
Green
GE30341X012 14 to 30 35 to 75 1 psig 69 1.2 psig 83 1.3 psig 90 2.1 psig 0.14 bar 2 psig 0.14 bar
Dark
Blue
GE30342X012
1 to
2.5 psig
69 mbar to
0.17 bar
2 psig 0.14 bar 2.6 psig 0.17 bar 2.6 psig 0.18 bar 3.8 psig 0.26 bar 3.7 psig 0.26 bar
Yellow GE30343X012
2.5 to
5.5 psig
0.17 to
0.38 bar
5 psig 0.34 bar 6.3 psig 0.43 bar 6.3 psig 0.43 bar 7.4 psig 0.51 bar 8.2 psig 0.56 bar
1. Downstream pressure buildup with Secondary Seat xed bleed in operation and regulator relief valve relieving to atmosphere.
2. Outlet pressure values listed are at maximum operating inlet pressure rating per orice. See Table 4.
3. If the outlet pressure rises above setpoint exceeds 3 psig / 207 mbar, inspect internal parts and replace if damaged.
Table 6. Approximate Internal Relief Valve Start-to-Discharge Pressure above Setpoint
CONTROL
SPRING
SETPOINT SET RANGE
INTERNAL RELIEF AND
HIGH CAPACITY RELIEF
TOKEN RELIEF
Start-to-Discharge Pressure
Range above Setpoint
Low Start-to-Discharge
Option
(1)
Start-to-Discharge Pressure
Range above Setpoint
Start-to-Discharge Pressure
Range above Setpoint
In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar
GE30337X012 4 10 3.5 to 6 9 to 15 11 to 18 27 to 42 7 to 14 17 to 35 6 to 14 15 to 35
GE30338X012 7 17 5.5 to 8.5 13 to 21 11 to 18 27 to 42 7 to 14 17 to 35 6 to 14 15 to 35
GE49043X012
(LIN)
7 17 5.5 to 8.5 13 to 21 11 to 18 27 to 42 7 to 14 17 to 35 6 to 14 15 to 35
GE30339X012 11 27 8 to 12 20 to 30 11 to 18 27 to 42 7 to 14 17 to 35 6 to 14 15 to 35
GE30340X012 14 35 10 to 16 25 to 40 11 to 18 27 to 42 7 to 14 17 to 35 6 to 14 15 to 35
GE30341X012 1 psig 69 14 to 30 35 to 75
7 in. w.c. to
1 psig
17 to 69 - - - - - - - - 8 to 16 20 to 40
GE30342X012 2 psig 138
1 to
2.5 psig
70 to 170
7 in. w.c. to
2 psig
17 to 138 - - - - - - - -
7 in. w.c. to
1 psig
17 to 69
GE46922X012 3 psig 207
1.5 to
3.5 psig
100 to 240
7 in. w.c. to
2 psig
17 to 138 - - - - - - - -
0.5 to
1.5 psig
35 to 100
GE30343X012 5 psig 345
2.5 to
5.5 psig
170 to 380
7 in. w.c. to
2.5 psig
17 to 170 - - - - - - - - 1 to 2 psig 69 to 138
1. Low start-to-discharge option is only available on the main control spring ranges up to 10 to 16 in. w.c. / 25 to 40 mbar.