Type EZH Relief or Backpressure Regulator
4
CAUTION
When installing Type EZH trim in an existing
Fisher
®
E-body, damage can result if ow is not
in the correct direction. Look at the body web
to conrm that ow is in the correct direction—
up through the center of the cage and down
through the cage slots. Change the existing
ow arrow if necessary.
After assembly, check for shutoff and leakage
to atmosphere.
2. A Type EZH relief valve or backpressure regulator may
be installed in any orientation, as long as ow through it
matches the direction of the arrow on the main valve body.
3. Apply pipe compound to the external pipeline threads
before installing a relief valve or backpressure regulator
with threaded NPT end connections. Use gaskets between
pipeline and relief valve or backpressure regulator anges
when installing a relief valve or backpressure regulator
with anged end connections. When installing butt weld
end connections, remove trim before welding and make
sure to use approved welding practices. Use approved
piping procedures when installing the relief valve or
backpressure regulator.
!
WARNING
When used in relief valve service, the Type EZH
main valve and pilot both exhaust gas. In
hazardous or ammable gas service, personal
injury, death, or property damage may occur
due to re or explosion of vented gas that
has accumulated. To prevent such injury or
damage, provide piping or tubing to vent the
gas to a safe location. The exhaust piping
must be designed and installed to guard
against excessive ow restriction. This piping
must be protected against condensation or
debris that could clog it.
For safety during shutdown, vent valves
are required immediately upstream
and downstream of the main valve on a
backpressure or bypass installation.
4. If system operation during maintenance is required, install
isolating and vent valves as needed.
5. For the Type PRX/182 pilot, if the vent assembly (key 12,
Figure 7) remains in the pilot body (key 1, Figure 7), then
it must be pointed down if possible or otherwise protected.
If the exhaust is to be piped to the main valve exhaust or
remotely vented, remove the vent assembly and install
tubing or piping into the 1/4 NPT pilot exhaust connection.
Protect the open end of the exhaust pipe by installing a
screened vent cap.
Type EZH
Type EZH Single-Pilot Relief Valve or
Backpressure Regulator
Type EZH Adjustment
The adjustment of setpoint (Figure 7), is performed by means
of the pilot adjusting screw, which varies the compression of
the control spring. Adjustment is performed while the relief
valve or backpressure regulator is in operation with the aid of a
pressure gauge to monitor upstream pressure.
Loosen the Type PRX pilot locknut and turn the adjusting screw
slowly clockwise to increase set pressure and counterclockwise
to decrease set pressure. Use a pressure gauge to monitor
the set pressure until the desired opening pressure is reached.
CAUTION
Personal injury or equipment damage, due
to bursting of pressure-containing parts may
result if this relief valve or backpressure
regulator is overpressured or is installed
where service conditions could exceed the
product and pilot pressure ratings.
Installation
!
WARNING
Personal injury, equipment damage, or
leakage due to escaping gas or bursting of
pressure-containing parts may result if the
Type EZH is installed where its capabilities
can be exceeded or where conditions
exceed any ratings of the adjacent piping or
connections. To avoid this, install a Type EZH
relief valve or backpressure regulator where:
Service conditions are within unit
capabilities (including those in the
Specications section).
Service conditions are within applicable
codes, regulations, or standards.
Additionally, physical damage to the relief
valve or backpressure regulator could break
the pilot off the main valve, causing personal
injury and property damage due to escaping
gas. To avoid such injury or damage, install
the unit in a safe location.
1. Only personnel qualied through training and
experience should install, operate, and maintain a relief
valve or backpressure regulator. Before installation,
make sure that there is no damage to, or debris in
the main valve body or pilot. Also, make sure that all
tubing and piping are clean and unobstructed.