Type OS2
10
Table 19. Choice of BMS and Springs
Table 20. BMS Material
PSD Diaphragm Bellows Piston
0 to 20
20 to 72 (*)
72 to 100
AG 2.5
AG 5
Max. only
Min. only
Max. and Min.
(*) Choice between piston (regular) and bellows (optional). Bellows are recommended
if you require a small gap between releasing pressure, inlet pressure and exact
precision. Pistons do not facilitate minimum and maximum releasing.
Diaphragm Bellows Piston
Spring case Zinc-plated steel Stainless steel
Spring box Aluminum + Chromatation
Diaphragm Nitrile mesh
Piston Stainless steel
Bellows Stainless steel
Spring Zinc-plated steel
Adjustment screw Zinc-plated steel
Note
When the setpoint (max. or min.) falls
between the lowest and lowest point
possible, the precision may pass into a
superior range (example AG 2.5 —> AG 5). If
the point value is too close to that of the Pd,
the option RJGI tripping is recommended
(consult factory). In the case of two safety
manometric boxes (BMS) both boxes should
have a PSD > to the highest Pdo.
SELECTION OF BMS AND SPRINGS
Choose the type of safety manometric box (BMS) according
to: PMS, the type of releasing precision.
Choice of springs:
• Max. or Min. only
Take the spring with the highest point directly superior to
the releasing pressure required.
• Max. and Min.
Take the spring with the highest maximum point superior to
the maximum releasing pressure required or with the lowest
point inferior to the minimum tripping pressure required.
MATERIALS (BMS)
ADJUSTMENT (BMS)
Generally speaking, adjustments are carried out with the slam
shut valve closed. Only the detection stage is reset. Control of
the releasing value may be obtained by resetting the two stages.
!
WARNING
AUTHORIZED PERSONNEL ONLY
Risk of injury
After rearming, remove the reset key from
the stem. Do not put fingers in or near the
reset mechanism area.
CAUTION
Before any adjustment, check that the
spring range installed corresponds to the
required setpoint.
Type BMS 1 (Figures 17 to 19)
Releasing by Max. Only
• Adjusting the releasing screw Free the min. hook (key 2).
Then in the following conditions:
- no pressure in the safety manometric box (BMS),
- setpoint spring compressed so that the distance
between the releasing screw and the pin D1 no longer
increases, adjust the releasing screw (key 1) to
X = 1.5 mm (detection stage set). Jam nut (key 3).
• Adjusting the max. only releasing pressure
Admit the releasing pressure to Pdo.
Screw the adjustment screw (key 5) until detection stage
can be set.
Unscrew the adjustment screw (key 5) until detection
stage release.
Check the pressure value at the releasing point
(adjust if necessary).
Jam nut (key 4).
Releasing by Min. Only
• Adjusting the releasing screw and hook
Free the min. hook (key 2).
Then in the following conditions:
- setpoint spring decompressed (adjustment screw
(key 5) unscrewed),
- pressure equal to the releasing pressure required for
Pd min in the BMS,
adjust the releasing screw (key 1) to X = 2 mm (detection
stage set).
Jam nut (key 3).
Put the hook (key 2) into position and adjust Y = 1.5 mm
with nuts (key 6) and (key 7).
Jam nuts (key 6) and (key 7).
• Adjusting the min. only releasing pressure
Continue admitting the required releasing pressure. Screw
the adjustment screw (key 5) until detection stage release.
Check the pressure value at the releasing point
(adjust if necessary). Jam lock nut (key 4).
N22
X = distance between releasing
screw and pin D1
Y = distance between releasing
screw and pin D2
1
X
Y
D2
D1
3 5
7
6
2 4