Standard Pilots
OPTIONS
RPE (Electric Heater)
The RPE is used for reheating gas supplying pressure
reducing regulator pilots. It avoids the inconveniences
caused by freezing which occur during large pressure drops.
(See instruction manual NTARPE).
ADGE 1” (Pre-expansion Exchanger)
The ADGE 1” replaces the standard pre-expansion relay. It
permits the gas to be reheated beyond pre-expansion without
using external energy sources. (See instruction manual
NTAADGE1). See table 3 for standard con gurations.
Mass volume corrector
Flow limiter
Remote control setting
Contact factory
TERMS
Failure Modes
FO: Fail to Open
Regulator Opens in the case of failure mode
The regulator tends to automatically open in the case
of failure of the main diaphragm or when there is an
interruption of the energy required for the displacement of
the regulation unit.
FC: Fail to Close
Regulator Closes in the case of failure mode
The regulator tends to automatically close in the case
of failure of the main diaphragm or when there is an
interruption of the energy required for the displacement of
the regulation unit.
Equipment:
- FO design: EZHFO - EZHSO - BERTIN EZ NO
MPNO
- FC design: EZH - BERTIN EZ - MPNF
Type BMP 114 MD Double-Diaphragm Pilot
(Figure 5)
The manometric box is equipped with two integral
diaphragms. The volume between these two diaphragms is
related to the driving pressure of the actuator.
Failure of the upper diaphragm will cause balance between
the driving pressure and the outlet pressure. Failure of the
lower diaphragm will cause evacuation the driving pressure
to the atmosphere.
In both cases the equipment tends to close due to lack of
driving pressure (Fail to Close).
PRE-EXPANSION DETERMINATION
MIN NOMINAL MAX
EZR 0.50 0.80 1.50
K1000 0.25 0.50 1.00
MPS 3.00 6.00 8.00
Table 4. Pre-expansion per Regulator (bar)
(Superior to downstream pressure (Pd))
A104
Table 5. Adjustable Pre-expansion Differential for EZH,
EZH FO, EZHSO, MP, Bertin EZ,
Working Monitor Regulator
or CPV Metering
MIN NOMINAL MAX
MP Pd + 1.2 Pd + 2.4 Pd + 4.8
BERTIN EZ Pd + 1.2 Pd + 2.4 Pd + 4.8
MPS Pd + 2 Pd + 4 Pd + 4.8
EZH, EZH FO,
EZHSO
Pd + 1.7 Pd + 2 Pd + 3
A105
Table 6. Adjustable Pre-expansion Differential for
Type FO Regulators
ACTUATOR NOMINAL
MPNO
BERTIN EZ NO
269 Pd + 0.8
374 Pd + 1.1
Adjustable from 0.4 to 1.3 bar
Adjustable according to size of actuator (factory set)
A106
Europe, Middle East, and Africa Only