Quick Start Guide00825-0100-4728, Rev BDMay 2014Rosemount® 644H and 644R Smart Temperature Transmitters
May 201410Quick Start GuideRail mount transmitter and sensor1. Attach the transmitter to a suitable rail or panel.2. Attach the thermowell to the pipe
Quick Start Guide11May 2014Rail mount transmitter with threaded sensor1. Attach the transmitter to a suitable rail or panel.2. Attach the thermowell t
May 201412Quick Start GuideStep 5: Wire and apply powerWire the transmitter Wiring diagrams are located inside the terminal block cover.Figure 4. Se
Quick Start Guide13May 2014Ground the transmitterUngrounded thermocouple, mV, and RTD/Ohm inputsEach process installation has different requirements f
May 201414Quick Start GuideOption 31. Ground sensor wiring shield at the sensor, if possible. 2. Insure that the sensor wiring and signal wiring shiel
Quick Start Guide15May 2014Step 6: Perform a loop testThe Loop Test command verifies transmitter output, loop integrity, and operation of any recorder
May 201416Quick Start GuideProduct CertificationsApproved Manufacturing LocationsRosemount Inc. - Chanhassen, Minnesota, USARosemount Temperature GmbH
Quick Start Guide17May 2014Special Conditions for Safe Use (X):1. When no enclosure option is selected, the Model 644 Temperature Transmitter shall be
May 201418Quick Start GuideI1 ATEX Intrinsic SafetyCertificate: Baseefa03ATEX0499X [Headmount Fieldbus/Profibus]; BAS00ATEX1033X [Railmount HART]; Bas
Quick Start Guide19May 2014InternationalE7 IECEx FlameproofCertificate: IECEx FMG 12.0022XStandards Used: IEC 60079-0:2011, IEC 60079-1:2007-04, IEC 6
May 20142Quick Start GuideNOTICEThis installation guide provides basic guidelines for the Rosemount 644. It does not provide instructions for detailed
May 201420Quick Start GuideNK IECEx DustCertificate: IECEx FMG 12.0022XStandards Used: IEC 60079-0:2011, IEC 60079-1:2007-04, IEC 60079-31:2008Marking
Quick Start Guide21May 2014ChinaE3 China FlameproofCertificate: GYJ111385Standards Used: GB3836.1-2000, GB3836.2-2000, GB12476.1-2000Markings: Ex d II
May 201422Quick Start GuideI3 China Intrinsic SafetyCertificate: GYJ111384XStandards Used: GB3836.1-2000, GB3836.4-2000Markings: Ex ia IIC T4/T5/T6Spe
Quick Start Guide23May 2014When Options select Enhanced PerformanceTerminals of power supply (+, -)Terminals of sensor (1,2,3,4)3. This product compli
May 201424Quick Start GuideN3 China Type nCertificate: GYJ101421Standards Used: GB3836.1-2000, GB3836.8-2003Markings: Ex nA nL IIC T5/T6Special Condit
Quick Start Guide25May 2014CombinationsK1 combination of E1, I1, N1, NC, and NDK2 combination of E2 and I2K5 combination of E5 and I5K7 combination of
May 201426Quick Start GuideDeclaration of Conformity
Quick Start Guide27May 2014
May 201428Quick Start Guide
Quick Start Guide29May 2014
Quick Start Guide3May 2014Step 1: Configure (bench calibration)The 644 communicates using the field communicator (communication requires a loop resist
May 201430Quick Start Guide
Quick Start Guide31May 2014
Rosemount Inc. 8200 Market Boulevard Chanhassen, MN USA 55317T (US) (800) 999-9307T (Intnl) (952) 906-8888F (952) 906-8889Emerson Process ManagementAs
May 20144Quick Start GuideStep 2: Verify configurationThe traditional interface Fast Key sequences in Table 1 and Device Dashboard Fast Key Sequences
Quick Start Guide5May 2014Table 1. Traditional Interface Fast Key SequencesFunction Fast Keys Function Fast KeysActive Calibrator 1, 2, 2, 1, 3 Open
May 20146Quick Start GuideInput/verify Callendar Van-Dusen constantsIf sensor matching is being used with this combination of a transmitter and sensor
Quick Start Guide7May 2014Input/verify Callendar Van-Dusen constantsIf sensor matching is being used with this combination of a transmitter and sensor
May 20148Quick Start GuideStep 4: Mount the transmitterMount the transmitter at a high point in the conduit run to prevent moisture from draining into
Quick Start Guide9May 2014Typical universal head installationHead mount transmitter with threaded sensor1. Attach the thermowell to the pipe or proces