Bulletin 74.1:Y693
5
Table 2. Type Y693 Regulator Construction Materials
PART NAME
MATERIAL
Aluminum Lower Casing Version Steel or Stainless Steel Lower Casing Version
Body Castiron WCBsteelorStainlesssteel
Body Gasket Composition Composition
UnionNut - - - - Steel or Stainless steel
Spring case Aluminum Aluminum,WCBsteelorStainlesssteel
Lower casing Aluminum WCBsteelorStainlesssteel
Oriceandbiasspring Stainless steel Stainless steel
Pusher post and stem Aluminum Stainless steel
Lever assembly Steel Stainless steel
Diaphragm Nitrile (NBR) or Fluorocarbon (FKM) Nitrile (NBR) or Fluorocarbon (FKM)
Controlspring,springseatandsplitring Plated steel Plated steel
Diaphragm plate Aluminum and Steel Aluminum and Steel
Disk and O-rings
Nitrile (NBR) and Stainless steel, Fluorocarbon (FKM)
andStainlesssteel,PTFEandStainlesssteel
Nitrile (NBR) and Stainless steel or Fluorocarbon (FKM)
andStainlesssteelorPTFEandStainlesssteel
4. From Table 6, at 0.5 in. w.c. / 1 mbar set pressure
and40psiginletpressure,aTypeY693willow
8880SCFH/238Nm
3
/hnitrogen.Thissatisesthe
5729SCFH/154Nm
3
/h requirements.
Capacity Information
Table 6 gives typical nitrogen regulating capacities at
selected inlet pressures and outlet pressure settings.
Flows are in SCFH (60°F and 14.7 psia) of 0.97
specicgravitynitrogen.Forgasesofotherspecic
gravities, multiply the given capacity of nitrogen by
0.985, and divide by the square root of the appropriate
specicgravityofthegasrequired.Then,ifcapacityis
desiredinnormalcubicmetersperhoursat0°Cand
1.01325 bar, multiplySCFHby 0.0268.
Todeterminewide-openowcapacitiesforrelief
sizing,usethefollowingformula:
Q =
520
GT
3417
C
1
P
P
1
C
g
P
1
SIN DEG
where,
C
g
= gassizingcoefcientfromSpecicationstable
C
1
= C
g
/C
v
or33fromtheSpecicationstable
G = gasspecicgravity(air=1.0)
P
1abs
= inlet pressure, psia (add 14.7 psi to gauge inlet
pressure to obtain absolute inlet pressure)
Q = owrate,SCFH
T = absolute temperature in °R of gas at inlet (°F + 460)
Installation
The regulator may be installed in any position as
longastheowthroughthebodyisinthedirection
indicatedbytheowarrowattachedtothebody.Install
the regulator as close as possible to the blanketed
vessel using a straight run of pipe the same size or
larger as the regulator body. Position the body and/or
diaphragm spring case so it will not collect moisture or
debris into the screened vent and also be self draining
(as shown in Figure 3). If a block valve is required,
installafullowvalvebetweentheregulatorandthe
blanketed vessel.
Attach a downstream pressure control line to the
female connection in the lower spring case. The
female pressure connection is a 1/2 NPT in the steel
or Stainless steel lower spring case and a 3/4 NPT
forthealuminumlowerspringcase.Connectthe
other end of the control line to the vessel. To allow for
self-drainage, install the control line at an angle so that
any liquid material will drain away from the regulator.
See Figure 4 for the location of the external control line
connection.Externaldimensionsandconnectionsare
shown in Figure 4.