FRU Installation
AXP 1410 Installation and Use (6806800H70D)
72
4.4 Installing Fan Tray Modules
To prevent system damage, the operator must replace the fans within the recommended
service interval shown in the following table to prevent a decline in shelf operability. Make sure
the replacement FTM is available for exchange and ready to install.
When a fan is taken out of operation, the system manager will compensate for the loss by
increasing the speed of the remaining fans. Please read the following caution before replacing
any of the FTMs.
Service Interval for 1 FTM Temperature Range
Not recommended 40-55°C
Four hours 40°C maximum
Fans may continue to rotate after power is removed. Be careful to keep fingers away from
the bottom of the FTM enclosure.