12 Micro Motion
®
2-Wire Coriolis Flow and Density Meters
Input/output signals and power supply
User interface
Transmitter One passive 12–20 mA output
Isolated to ±50 VDC from earth ground
Maximum load limit: 600 Ω
External power: 17–36 VDC
•0,8W maximum
Can report mass flow, liquid volume flow, gas standard volume flow, density,
temperature, or drive gain
Output is linear with process from 11,9 to 20,25 mA
Adapter-barrier Power supply
18–42 VDC
Maximum supply current: 170 mA
Maximum power: 3 W
One active or passive 4–20 mA output
Maximum load limit (active output): < 1 kΩ
Maximum loop voltage (passive input): < 36 V
Linearity: < 0.05% span
One passive 12–20 mA input
HART pass-through
Loop supply: > 25 V
HART-compliant impedance: > 250 Ω
Compliant with ATEX, CSA, and IECEx intrinsic safety requirements
Conforms to NAMUR NE21 Version 08.22.2007
Standard user interface with LCD panel
Suitable for hazardous area installation.
User interface module can rotate 360° on the transmitter in 90° increments.
Two clips for HART/Bell 202 connections (requires removing transmitter housing cover).
Two membrane pushbuttons for local operation (requires removing transmitter
housing cover).
Depending on purchase option, transmitter housing cover has glass or plastic lens.
User interface module includes LCD panel. LCD line 1 displays process variable; line 2
displays engineering unit of measure, with optional alarm indication.
LCD panel can be configured to scroll through display list at user-specified scroll rate.
Display list includes user-selected process variables and, optionally, all active alarms.
Display update rate is user-configurable: 100 to 10000 milliseconds.