EZH and EZHSO Series
8
CAUTION
Personal injury or equipment damage,
due to bursting of pressure-containing
parts may result if this regulator is
overpressured or is installed where
service conditions could exceed the
regulator and pilot pressure ratings.
The working regulator must be rated
for the maximum allowable operating
pressure of the system because this will
be its inlet pressure if the monitoring
regulator fails. Also, the outlet pressure
rating of the monitoring pilot and any
other components that are exposed to
the intermediate pressure must be rated
for full inlet pressure.
Working monitor installations require an EZH or
EZHSO Series main valve with a Type PRX/120 or
PRX/120-AP working pilot and a Type PRX/125 or
PRX/125-AP monitoring pilot for the upstream
regulator and an EZH or EZHSO Series with the
appropriate Type PRX/120 or PRX/120-AP pilot for
the downstream regulator.
Adjustment
Adjusting the monitor regulator (Figure 6) is the same
as adjusting the main regulator. Monitor setpoints are
set slightly higher than the main regulator. The monitor
pressure setting should be adjusted so it is at minimum
two times the pilot accuracy band pressure above the
working regulator pressure setting. For the adjustment
of the monitor regulator’s two pilots, please refer to the
section on Startup and Adjustment on page 10.
Installation
!
WARNING
Personal injury or equipment damage,
due to bursting of pressure-containing
parts may result if this regulator is
overpressured or is installed where
service conditions could exceed the
limits given in the Specication section
and on the appropriate nameplate or
where conditions exceed any rating
of the adjacent piping or piping
connections. To avoid such injury or
Figure 6. Working Monitoring System Operational Schematics
E0876
EZH SERIES
WORKER REGULATOR
EZH SERIES
MONITOR REGULATOR
TYPE
PRX-120
TYPE
PRX-125
TYPE
PRX-120
TYPE
SA/2
CHECK
VALVE
CHECK VALVE
TYPE
SA/2
V
R
M
V
R
M
M
S
L
A
B
S
A
B
S
L
A
B
TYPE PRX
S - BLEED PORT
B - SUPPLY PORT
L - LOADING PORT
A - SENSING PORT
TYPE SA/2:
V - SENSING PORT
R - PILOT SUPPLY PORT
M - INLET PORT
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
INTERMEDIATE PRESSURE
PILOT SUPPLY PRESSURE
LOADING PRESSURE