Optional fea tures - all sys tems (con tin ued)
Short message manager (SMM)
If so configured, the Microface controller can send text
messages (SMS) about unit status or alarm conditions,
directly to the display of a GSM mobile phone, allowing quick
and cost effective maintenance. The Hirolink Light Interface
and a GSM modem are required.
Extended alarm board
For applications where remote indication of alarms is
required, a special extended alarm board is available.
As standard, a volt-free warning contact is available for
remote indication of High Temperature, Low Temperature
and Heater Overtemperature. A further contact is available
for remote indication of High Pressure, Low Pressure, Fan
Failure and Controls Failure.
The Alarm Board allows individual alarm outputs (up to five,
either normally closed or normally open) for:
High or Low refrigerant pressure; High Room Temperature;
Low Room Temperature; Fan Failure, Clogged Filter Alarm
(if installed).
No display
Where the units are connected in a network and controlled
from a central point or where a display is not required for
security purposes, the units can be ordered with no display.
Humidity control
If required, the unit can be supplied to control temperature and
humidity in the conditioned area, it is supplied as standard for
temperature control only.
External temperature sensor
An additional sensor can be provided to monitor the external
temperature and provide the information to a central network.
The sensor is not used in the control sequence of the unit.
Interconnection cables
A full range of interconnecting cables is available for
applications where the units are configured as Run and
Standby or where the controller display is mounted remotely
from the unit, consult Liebert Application Engineers for
specific details.
Filter clog switch
An adjustable diaphragm-type, differential pressure switch
can be fitted to initiate a change filter alarm when a
pre-selected pressure drop across the filter bank is exceeded.
Aluminium alloy cabinet
Please contact Liebert for details .
Special colours
The standard galvanised steel cabinet is available with the
following range of powder coated colours:
Olive Green (RAL 6002)
Blue Green (RAL 6004)
Moss Green (RAL 6005)
Bright Grey (RAL 7035)
Sepia Brown (RAL 8014)
Pure White (RAL 9010)
Epoxy coated coils
If the unit is to be installed in a potentially corrosive
environment or close to salt water, epoxy/acrylic coated fins
on the condenser and evaporator coil are available to
maximise unit operating life.
8 SLE ICX TDM E.2 (06/99)
InteleCool EX - Technical Data Manual