Figure 8. Type EZR X Body with Integral OS2 Slam Shut and PRX Pilot
B18B
Slam Shut
The pressure of the zone to be protected (generally the
pipeline on the outlet side of the regulator and after the slam
shut) is sensed by the safety manometric box (BMS).
If the pressure exceeds the set tripping pressure, the
release relay frees the valve plug.
Due to the force of the closing spring and the uid (trying to
close), the valve plug closes on the seat.
The gas ow is obstructed until the fault has been corrected
and the mechanism box manually rearmed.
To reopen the valve plug an equal pressure balance on inlet
and outlet sides of the regulator is required.
The mechanism box is rearmed after opening the
internal bypass.
Rearming and balancing are achieved at the same time.