Reference Manual 00809-0100-4808, Rev CAJune 2008www.rosemountnuclear.comRosemount 3051N Smart Pressure Transmitter for Nuclear Service
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NTOC-4Multifunction LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NThe Emerson logo is a trade mark and service mark of Emerson Electric Co. Rosemount and
Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comSection 1 IntroductionUSING THIS MANUAL The sections in this m
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N1-2
Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comSection 2 Transmitter FunctionsOverview . . . . . . . . . . .
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-2FAILURE MODE ALARM Rosemount 3051N transmitters automatically and continuously perfo
Reference Manual 00809-0100-4808, Rev CAJune 20082-3Rosemount 3051N1. Security Jumper: prevents all writes to transmitter configuration.2. Local Keys
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-4FIGURE 2-1. Electronics Board.FIGURE 2-2. Rosemount 3051N with Optional LCD Meter.CO
Reference Manual 00809-0100-4808, Rev CAJune 20082-5Rosemount 3051NTo commission on the bench, connect the transmitter and the communicator as shown i
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-6Wiring Diagrams (Field Hook-up)The following diagrams illustrate wiring loops for a
Reference Manual 00809-0100-4808, Rev CAJune 20082-7Rosemount 3051NREVIEW CONFIGURATION DATANOTEInformation and procedures in this section that make u
IMPORTANT NOTICE -- ERRATA Model 3051N Product Manual 00809-0100-4808 Rev CA (6/2008) No. Affected Pages Description of Change Effect. Date 1 5-8
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-8NOTERegardless of the range points, the Rosemount 3051N will measure and report all
Reference Manual 00809-0100-4808, Rev CAJune 20082-9Rosemount 3051NFIGURE 2-5. Square Root Output Transition Point.Rerange The Range Values command se
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-10NOTEIf the transmitter security jumper is in the ON position, you will not be able
Reference Manual 00809-0100-4808, Rev CAJune 20082-11Rosemount 3051NTo rerange the transmitter using the span and zero buttons, perform the following
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-12Damping The process variable (PV) Damp command changes the response time of the tra
Reference Manual 00809-0100-4808, Rev CAJune 20082-13Rosemount 3051NTransmitter Test The transmitter Self Test command initiates a more extensive diag
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-14Smart transmitters operate differently than analog transmitters. A smart transmitte
Reference Manual 00809-0100-4808, Rev CAJune 20082-15Rosemount 3051NCalibration Overview Complete calibration of the Rosemount 3051N Pressure Transmit
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-16FIGURE 2-7. Transmitter Data Flow with Calibration Options.Deciding Which Trim Proc
Reference Manual 00809-0100-4808, Rev CAJune 20082-17Rosemount 3051NWhen performing a zero trim, ensure that the equalizing valve is open and all wet
Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comRosemount 3051N Smart Pressure Transmitter for Nuclear Service
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-18Full Trim To calibrate the sensor with a HART Communicator using the full trim func
Reference Manual 00809-0100-4808, Rev CAJune 20082-19Rosemount 3051NRecall Factory Trim The Recall Factory Trim commands allow the restoration of the
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-20NOTEUse a precision resistor for optimum accuracy. If you add a resistor to the loo
Reference Manual 00809-0100-4808, Rev CAJune 20082-21Rosemount 3051NHTc = URV + S (URV) Ps In this example: To calculate the corrected low trim (LTc)
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-22
Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comSection 3 InstallationOverview . . . . . . . . . . . . . . .
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N3-2Replacement equipment or spare parts not approved by Rosemount Nuclear Instruments,
Reference Manual 00809-0100-4808, Rev CAJune 20083-3Rosemount 3051NFIGURE 3-1. Typical Installation Flowchart.START HEREBench Calibration?Field Instal
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N3-4GENERAL CONSIDERATIONSMeasurement accuracy depends upon proper installation of the t
Reference Manual 00809-0100-4808, Rev CAJune 20083-5Rosemount 3051NNOTEFor steam service, do not blow down impulse piping through the transmitter. Flu
iiReference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NRosemount Nuclear Instruments, Inc. Warranty and Limitations of RemedyThe warranty an
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N3-6FIGURE 3-3. Rosemount 3051N Coplanar Flange Dimensional Drawing (Differential Pressu
Reference Manual 00809-0100-4808, Rev CAJune 20083-7Rosemount 3051NFIGURE 3-4. Traditional Flange Mounting Configurations with Optional Brackets for P
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N3-8FIGURE 3-5. Traditional Flange (Option Code H2) Dimensional DrawingTerminal connecti
Reference Manual 00809-0100-4808, Rev CAJune 20083-9Rosemount 3051NMounting The Rosemount 3051N Pressure Transmitter weighs approximately 6.0 lb (2,7
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N3-10NOTEIn steam or other elevated temperature services, it is important that temperatu
Reference Manual 00809-0100-4808, Rev CAJune 20083-11Rosemount 3051NFIGURE 3-6. Typical Installation Examples to Illustrate Transmitter and Impulse Pi
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N3-12Process Connections Rosemount 3051N connections on the transmitter flange are 1/4–1
Reference Manual 00809-0100-4808, Rev CAJune 20083-13Rosemount 3051NFIGURE 3-7. Power Supply Load Limitations.Wiring To make connections, perform the
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N3-14Grounding the Transmitter CaseThe transmitter case should always be grounded in acc
Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comSection 4 TroubleshootingOverview . . . . . . . . . . . . . .
Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comRevision StatusChanges from June 2006 to June 2008NOTEThe abov
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N4-2Table 4-1. Rosemount 3051N Troubleshooting Chart.The Rosemount 3051N is supplied by
Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comSection 5 Specifications and Reference DataNuclear Specificati
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N5-2Environmental Performance to normal operating limits as described in the “Performanc
Reference Manual 00809-0100-4808, Rev CAJune 20085-3Rosemount 3051NPERFORMANCE SPECIFICATIONSBased upon zero-based calibrations, reference conditions,
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N5-4Overpressure Effect Maximum zero shift after overpressure equal to Maximum Working P
Reference Manual 00809-0100-4808, Rev CAJune 20085-5Rosemount 3051NFUNCTIONAL SPECIFICATIONSServiceLiquid, gas, or vaporOutput 4–20 mA, user-selectabl
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N5-6Span and Zero, Zero Elevation, and SuppressionZero and span values can be set anywhe
Reference Manual 00809-0100-4808, Rev CAJune 20085-7Rosemount 3051NFigure 5-1. Typical Smart Transmitter Response TimeMaximum Working Pressure(1)(2)Ro
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N5-8PHYSICAL SPECIFICATIONSMATERIALS OF CONSTRUCTIONIsolating Diaphragms316L SSTDrain/Ve
Reference Manual 00809-0100-4808, Rev CAJune 20085-9Rosemount 3051NOption Code Description Add:J Stainless Steel Housing 3.1 lb (1.4 kg)H2 Traditional
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051Niv
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N5-10ORDERING INFORMATIONRosemount 3051N(1) Differential, Gage, and Absolute Pressure Tr
Reference Manual 00809-0100-4808, Rev CAJune 20085-11Rosemount 3051NNOTEMounting Bracket option code must be specified last in the Rosemount model num
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N5-12ROSEMOUNT 3051N 4-20 MA/HART OUTPUT SMART PRESSURE TRANSMITTERS TYPICAL CONFIGURATI
Reference Manual 00809-0100-4808, Rev CAJune 20085-13Rosemount 3051NHARDWARE SELECTABLE INFORMATIONAlarm Option: High★ Low Transmitter Security:
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N5-14Figure 5-2. Rosemount 3051N Exploded View (with Coplanar Process Flange).LabelElect
Reference Manual 00809-0100-4808, Rev CAJune 20085-15Rosemount 3051N
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N5-16
Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comSection 6 OptionsOverview . . . . . . . . . . . . . . . . . .
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N6-2The meter features a two-line display with five digits for reporting the process var
Reference Manual 00809-0100-4808, Rev CAJune 20086-3Rosemount 3051Na. Select 5 CM xfer fnct. Enter the transmitter transfer function for the meter. Se
Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comTable of ContentsSECTION 1IntroductionUsing This Manual . . .
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N6-44. Insert the interconnection header in the ten-pin socket exposed by removal of the
Reference Manual 00809-0100-4808, Rev CAJune 20086-5Rosemount 3051NFIGURE 6-2. Rosemount 3051N with Optional LCD Meter.Diagnostic Messages In addition
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N6-6Some non-volatile memory faults are user-addressable. Use a HART Communicator to dia
Reference Manual 00809-0100-4808, Rev CAJune 20086-7Rosemount 3051NOperation Normal operation messages appear on the LCD meter to confirm actions or i
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N6-8Option PM is a SST pipe mount bracket assembly designed for use in pipe mounting the
Reference Manual 00809-0100-4808, Rev CAJune 20086-9Rosemount 3051NFIGURE 6-4. Transient Protection Terminal Block (T1).
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N6-10
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comAppendix A HART CommunicatorIntroduction . . . . . . . . . . .
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-2WarningsExplosions can result in death or serious injury.• Do not remove the transmi
Reference Manual00809-0100-4808, Rev CAJune 2008A-3Rosemount 3051NFIGURE A-1. HART Communicator Typical Abbreviated Menu Tree for Rosemount 3051.1 DEV
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NTOC-2Zero Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-4Table A-1. Typical HART Fast Key Sequences for the Rosemount 3051 (partial listing)
Reference Manual00809-0100-4808, Rev CAJune 2008A-5Rosemount 3051NCONNECTIONS AND HARDWAREThe HART Communicator can interface with a transmitter from
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-6FIGURE A-4. Bench Hook-up(4–20 mA Transmitters).FIGURE A-5. Field Hook-up(4–20 mA Tr
Reference Manual00809-0100-4808, Rev CAJune 2008A-7Rosemount 3051NROSEMOUNT 275Communicator Keys The keys of the Rosemount 275 HART Communicator inclu
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-8Hot KeyUse this key to quickly access important, user-selectable options when connec
Reference Manual00809-0100-4808, Rev CAJune 2008A-9Rosemount 3051NFast Key Sequences HART fast key sequences provide quick on-line access to most tran
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-10NOTEOnline communication with the transmitter automatically loads the current trans
Reference Manual00809-0100-4808, Rev CAJune 2008A-11Rosemount 3051NROSEMOUNT 375Communicator Keys The keys of the Rosemount 375 HART Communicator incl
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-12Enter KeyThe enter ( ) key allows you to launch the focused item or to complete an
Reference Manual00809-0100-4808, Rev CAJune 2008A-13Rosemount 3051NUsing the Soft Input Panel (SIP) keyboardThe SIP keyboard allows for alphanumeric i
Reference Manual 00809-0100-4808, Rev CAJune 2008TOC-3Rosemount 3051NTemperature Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-14Fast Key Sequences The Fast Key sequence is a sequence of numerical button presses,
Reference Manual00809-0100-4808, Rev CAJune 2008A-15Rosemount 3051NAdd item for ALL device types or only for this ONE device type.Asks the user whethe
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-16Looking for a device Polling for multidropped devices at addresses 1–15.Local butto
Reference Manual00809-0100-4808, Rev CAJune 2008A-17Rosemount 3051NROM checksum error ONChecksum of transmitter software has detected a fault. Return
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-18Value out of range The user-entered value is either not within the range for the gi
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comGlossaryAnalog Output Trim Digital Trim operation that allows a
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NG-2Lower Range Value (LRV) Lowest value of the measured variable that the analog output
Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comIndexAAccess Requirements . . . . . . 3-14Alarm and Security J
Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NIndex-2SSecurity . . . . . . . . . . . . . . . . 2-2Local Zero and Span Physical Remo