Reference Manual
00809-0100-4801, Rev FA
October 2010
3-25
Rosemount 3051S Series
AMS v7.0
Right click on the device and select “Configure”.
1. In “Basic Setup” tab, locate “Variable Mapping” box.
2. Choose desired primary variable.
3. Choose desired secondary variable.
4. Choose desired tertiary variable.
5. Click Apply and then select Next to acknowledge the loop can be
returned to automatic control.
6. Select Finish to acknowledge the method is complete.
Sensor Temperature Unit The Sensor Temperature Unit command selects between Celsius and
Fahrenheit units for the sensor temperature. The sensor temperature output
is accessible via HART only.
Field Communicator v3.3
Enter the fast key sequence “Sensor Temperature Unit.”
AMS v7.0
Right click on the device and select “Configure” from the menu
.
1. In the “Process Input” tab, use the drop down menu “Snsr temp unit” to
select F (Farenheit) or C (Celsius). Click Apply.
2. Click Next to acknowledge send warning.
3. Select Finish to acknowledge the method is complete.
4. After carefully reading the warning, select yes.
DIAGNOSTICS AND
SERVICE
Diagnostics and service functions listed below are primarily for use after field
installation. The Transmitter Test feature is designed to verify that the
transmitter is operating properly, and can be performed either on the bench or
in the field. The Loop Test feature is designed to verify proper loop wiring and
transmitter output, and should only be performed after you install the
transmitter.
Traditional Fast Keys
1, 4, 1, 2, 2
Device Dashboard
Fast Keys
2, 2, 1, 6