Product Data SheetSeptember 201400813-0100-4001, Rev SARosemount 3051 Pressure TransmitterWith the Rosemount 3051 Pressure Transmitter, you’ll gain mo
10Rosemount 3051September 2014www.rosemount.com(8) Materials of Construction comply with recommendations per NACE MR0175/ISO 15156 for sour oil field
11Rosemount 3051September 2014www.rosemount.comRosemount 3051T In-Line Pressure TransmitterSee “Specifications” on page 45 and options for more detail
12Rosemount 3051September 2014www.rosemount.comIsolating diaphragm Process connection wetted parts material2(10)316L SST 316L SST H3(10)Alloy C-276 Al
13Rosemount 3051September 2014www.rosemount.comIA ATEX Intrinsic Safety for FISCO; for FOUNDATION fieldbus or PROFIBUS PA protocols only HN1 ATEX Type
14Rosemount 3051September 2014www.rosemount.comConfiguration buttonsD4(22)Analog Zero and Span HDZ(23)Digital Zero Trim HDisplay and interface optio
15Rosemount 3051September 2014www.rosemount.comNACE certificateQ15(29)Certificate of Compliance to NACE MR0175/ISO15156 for wetted materials HQ25(29)C
16Rosemount 3051September 2014www.rosemount.com(26) The T1 option is not needed with FISCO Product Certifications; transient protection is included in
17Rosemount 3051September 2014www.rosemount.comRosemount 3051CF Flowmeter Selection GuideRosemount 3051CF Flowmeters combine the proven Rosemount 3051
18Rosemount 3051September 2014www.rosemount.comRosemount 3051CFA Annubar FlowmeterThe Rosemount 3051CFA Annubar Flowmeter utilizes the T-shaped sensor
19Rosemount 3051September 2014www.rosemount.com160 16-in. (400 mm)180 18-in. (450 mm)200 20-in. (500 mm)240 24-in. (600 mm)300 30-in. (750 mm)360 36-i
2Rosemount 3051September 2014www.rosemount.comSetting the Standard for Pressure MeasurementProven best-in-class performance, reliability and safety O
20Rosemount 3051September 2014www.rosemount.comSensor size1 Sensor size 1 — Line sizes 2-in. (50 mm) to 8-in. (200 mm) H2 Sensor size 2 — Line sizes 6
21Rosemount 3051September 2014www.rosemount.comTransmitter connection platform3 Direct-mount, Integral 3-valve Manifold– not available with Flanged mo
22Rosemount 3051September 2014www.rosemount.comPressure testingP1(10)Hydrostatic Testing with CertificatePX(10)Extended Hydrostatic TestingSpecial cle
23Rosemount 3051September 2014www.rosemount.comSpecial shipmentY1 Mounting Hardware Shipped Separately HSpecial dimensionsVM Variable MountingVT Varia
24Rosemount 3051September 2014www.rosemount.comShipboard approvalsSBS(18)American Bureau of Shipping HSLL(18)(19) Lloyds Register (LR)Display and inte
25Rosemount 3051September 2014www.rosemount.com(4) Option HR5 configures the HART output to HART Revision 5. Option HR7 configures the HART output to
26Rosemount 3051September 2014www.rosemount.comRosemount 3051CFC Compact FlowmeterRosemount 3051CFC Compact Flowmeters provide a quick, reliable insta
27Rosemount 3051September 2014www.rosemount.comPrimary element typeN000 Annubar Sensor Size 1 HN040 0.40 Beta Ratio HN050 0.50 Beta RatioN065(4)0.65 B
28Rosemount 3051September 2014www.rosemount.comInstallation accessoriesAB ANSI Alignment Ring (150#) (Only required for 10-in. (250 mm) and 12-in. (30
29Rosemount 3051September 2014www.rosemount.comIA ATEX FISCO Intrinsic Safety; for FOUNDATION fieldbus or PROFIBUS PA protocols only HN1 ATEX Type n a
3Rosemount 3051September 2014www.rosemount.comIndustry leading capabilities extended to IEC 62591 (WirelessHART®) Cost effectively implement wireless
30Rosemount 3051September 2014www.rosemount.comAlarm levelsC4(14)NAMUR Alarm and Saturation Levels, High Alarm HCN(14)NAMUR Alarm and Saturation Level
31Rosemount 3051September 2014www.rosemount.com(22) Only valid with FOUNDATION fieldbus (output code F).(23) The V5 option is not needed with the T1 o
32Rosemount 3051September 2014www.rosemount.comRosemount 3051CFP Integral Orifice FlowmeterRosemount 3051CFP Integral Orifice Flowmeters enable highly
33Rosemount 3051September 2014www.rosemount.comA3 Pipe Ends: Flanged, RF, ANSI Class 300, slip-onA6 Pipe Ends: Flanged, RF, ANSI Class 600, slip-onR1
34Rosemount 3051September 2014www.rosemount.comTransmitter outputA(3)4–20 mA with digital signal based on HART Protocol HF FOUNDATION fieldbus Protoco
35Rosemount 3051September 2014www.rosemount.comMaterial examinationV2 Radiographic ExaminationFlow calibrationWD(11)Discharge Coefficient Verification
36Rosemount 3051September 2014www.rosemount.comE3 China Flameproof HI3 China Intrinsic Safety HKB FM and CSA Explosion-proof, Dust Ignition-proof, Int
37Rosemount 3051September 2014www.rosemount.com(5) Requires wireless options and engineered polymer housing. Available approvals are FM Intrinsically
38Rosemount 3051September 2014www.rosemount.comRosemount 3051L Level TransmitterSee Specifications and options for more details on each configuration
39Rosemount 3051September 2014www.rosemount.comA6(6)3-in./DN 80 316L SST 6-in./150 mm HB0(6)4-in./DN 100 316L SST Flush Mount HB2(6)4-in./DN 100 316L
4Rosemount 3051September 2014www.rosemount.comRosemount 3051C Coplanar™ Pressure TransmitterSee Specifications and options for more details on each c
40Rosemount 3051September 2014www.rosemount.comMounting flange size, rating, material (high side)Size Rating MaterialW(6)DN 100 PN 10/16 per EN 1092-1
41Rosemount 3051September 2014www.rosemount.comO-ringA Glass-filled PTFE HHousing material Conduit entry sizeA Aluminum ½–14 NPT HB Aluminum M20 × 1.5
42Rosemount 3051September 2014www.rosemount.comC6 CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, and Division 2 HI6(8)CSA Intrinsic Saf
43Rosemount 3051September 2014www.rosemount.comToolkit total system performance reportsQZ Seal System Performance Calculation Report HConduit electri
44Rosemount 3051September 2014www.rosemount.comNACE certificateQ15(23)Certificate of Compliance to NACE MR0175/ISO 15156 for wetted materials HQ25(23)
45Rosemount 3051September 2014www.rosemount.comSpecificationsPerformance specificationsThis product data sheet covers HART, Wireless, FOUNDATION field
46Rosemount 3051September 2014www.rosemount.comTotal performanceTotal performance is based on combined errors of reference accuracy, ambient temperatu
47Rosemount 3051September 2014www.rosemount.comDynamic performanceLine pressure effect per 1000 psi (68,95 bar)Ambient temperature effect per 50 °F (2
48Rosemount 3051September 2014www.rosemount.comMounting position effectsVibration effectLess than ±0.1% of URL when tested per the requirements of IEC
49Rosemount 3051September 2014www.rosemount.comFunctional specificationsRange and sensor limits Table 7. 3051CD, 3051CG, 3051CF, and 3051L Range and S
5Rosemount 3051September 2014www.rosemount.comMaterials of constructionProcess flange type Flange material Drain/vent2 Coplanar SST SST H3(8)Coplanar
50Rosemount 3051September 2014www.rosemount.comServiceLiquid, gas, and vapor applications4-20 mA HART (output code A)Power supplyExternal power supply
51Rosemount 3051September 2014www.rosemount.comLCD transducer blockThe LCD transducer block is used to configure the LCD display meter.Analog input bl
52Rosemount 3051September 2014www.rosemount.comLocal operator interfaceThe LOI utilizes a 2 button menu with external configuration buttons.Wireless (
53Rosemount 3051September 2014www.rosemount.com3051T In-LineRanges 1-4: 11016 psi (759,53 bar)Range 5: 26016 psig (1793,74 bar)Failure mode alarmHART
54Rosemount 3051September 2014www.rosemount.comDamping4-20 mA HARTAnalog output response to a step input change is user-enterable from 0.0 to 60 secon
55Rosemount 3051September 2014www.rosemount.comBoltsPlated carbon steel per ASTM A449, Type 1Austenitic 316 SST per ASTM F593ASTM A193, Grade B7M allo
56Rosemount 3051September 2014www.rosemount.com3051 Product CertificationsEuropean Directive InformationA copy of the EC Declaration of Conformity can
57Rosemount 3051September 2014www.rosemount.comEuropeE8 ATEX Flameproof and DustCertificate: KEMA00ATEX2013X; Baseefa11ATEX0275XStandards Used: EN600
58Rosemount 3051September 2014www.rosemount.comInternationalE7 IECEx Flameproof and DustCertificate: IECEx KEM 09.0034X; IECEx BAS 10.0034XStandards:
59Rosemount 3051September 2014www.rosemount.comBrazilE2 INMETRO FlameproofCertificate: UL-BR 13.0643XStandards: ABNT NBR IEC60079-0:2008 + Errata 1:20
6Rosemount 3051September 2014www.rosemount.comOptions (include with selected model number)Extended product warrantyWR3 3-year limited warranty HWR5 5-
60Rosemount 3051September 2014www.rosemount.comhazardous location. When used in combustible dust environment, cable entry in accordance with IP66 or h
61Rosemount 3051September 2014www.rosemount.comlimitation-Selection, installation and maintenance”GB15577-2007 “Safety regulations for dust explosion
62Rosemount 3051September 2014www.rosemount.comSpecial Conditions for Safe Use (X):1. When the thread adapter or blanking plug is used with an enclosu
63Rosemount 3051September 2014www.rosemount.comFCC and ICThis device complies with Part 15 of the FCC Rules. Operation is subject to the following con
64Rosemount 3051September 2014www.rosemount.comPipe I.D. Range CodesFor pipes with an Inner Diameter (I.D.) Range/Pipe Wall Thickness not found in thi
65Rosemount 3051September 2014www.rosemount.comSensor Size 16-in. (150 mm)6.93-in. (176.02 mm)0605.250 to 5.472-in. (133.35 to 138.99 mm)0.134 to 0.61
66Rosemount 3051September 2014www.rosemount.comRosemount 3051 Dimensional Drawings(1)Figure 1. Rosemount 3051C Exploded View(1) This section contains
67Rosemount 3051September 2014www.rosemount.comFigure 2. Rosemount 3051C Coplanar FlangeFigure 3. 3051 Wireless Housing with Coplanar FlangeDimensions
68Rosemount 3051September 2014www.rosemount.comFigure 4. Rosemount 3051C Coplanar Flange with Rosemount 305RC3 3-Valve Coplanar Integral ManifoldDimen
69Rosemount 3051September 2014www.rosemount.comFigure 5. Coplanar Flange Mounting Configurations with Optional Bracket (B4) for 2-in. Pipe or Panel Mo
7Rosemount 3051September 2014www.rosemount.comProduct certificationsE8 ATEX Flameproof and Dust Certification HI1(21)ATEX Intrinsic Safety and Dust HI
70Rosemount 3051September 2014www.rosemount.comFigure 6. Rosemount 3051C Coplanar with Traditional FlangeFigure 7. Rosemount 3051C Coplanar with Rosem
71Rosemount 3051September 2014www.rosemount.comFigure 8. Traditional Flange Mounting Configurations with Optional Brackets for 2-in. Pipe or Panel Mou
72Rosemount 3051September 2014www.rosemount.comFigure 9. Rosemount 3051T Dimensional DrawingsFigure 10. 3051T Wireless Housing Dimensional DrawingsDim
73Rosemount 3051September 2014www.rosemount.comFigure 11. Rosemount 3051T with Rosemount 306 2-Valve I Integral ManifoldFigure 12. Rosemount 3051T Typ
74Rosemount 3051September 2014www.rosemount.comFigure 13. Rosemount 3051CFA Pak-Lok Annubar Flowmeter(1)Front view Side view Top view(1) The Pak-Lok A
75Rosemount 3051September 2014www.rosemount.comFigure 14. Rosemount 3051CFC Compact Orifice FlowmeterOrifice plate side view Orifice plate front view
76Rosemount 3051September 2014www.rosemount.comFigure 15. Rosemount 3051CFP Integral Orifice FlowmeterSide viewBottom view Front viewA. B.D. (Bore Dia
77Rosemount 3051September 2014www.rosemount.comFigure 16. Rosemount 3051L Dimensional Drawings2-in. flange configuration (flush mount only) 3- and 4-i
78Rosemount 3051September 2014www.rosemount.comDiaphragm assembly and mounting flangeDimensions are in inches (millimeters).5.13(130)4.29(109)6.80(173
79Rosemount 3051September 2014www.rosemount.com Table 15. 3051L Dimensional SpecificationsClass(1)Pipe sizeFlange thickness ABolt circle diameter HOu
8Rosemount 3051September 2014www.rosemount.comBolting materialL4 Austenitic 316 SST Bolts HL5 ASTM A 193, Grade B7M Bolts HL6 Alloy K-500 Bolts HDispl
80Rosemount 3051September 2014www.rosemount.comOptionsStandard configurationUnless otherwise specified, transmitter is shippedas follows:Custom config
81Rosemount 3051September 2014www.rosemount.comCommissioning tag(1)A temporary commissioning tag is attached to all transmitters. The tag indicates th
82Rosemount 3051September 2014www.rosemount.comRosemount 3051C Traditional Flange Bracket OptionsB1 Bracket for 2-in. Pipe Mounting• For use with the
83Rosemount 3051September 2014www.rosemount.com
Standard Terms and Conditions of Sale can be found at www.rosemount.com\terms_of_saleThe Emerson logo is a trade mark and service mark of Emerson Elec
9Rosemount 3051September 2014www.rosemount.comCleaning process areaP2 Cleaning for Special ServiceP3 Cleaning for <1 PPM Chlorine/FluorineFlange ad