Reference Manual
00809-0100-4001, Rev JA
Section 2: Installation
November 2012
Installation
2.8.4 Inline process connection
Inline gage transmitter orientation
The low side pressure port on the inline gage transmitter is located in the neck of the
transmitter, behind the housing. The vent path is 360 degrees around the transmitter between
the housing and sensor (See Figure 2-10).
Keep the vent path free of any obstruction, such as paint, dust, and lubrication by mounting the
transmitter so that the process can drain away.
Figure 2-10. Inline gage low side pressure port
2.8.5 Housing rotation
The electronics housing can be rotated up to 180 degrees in either direction to improve field
access, or to better view the optional LCD display. To rotate the housing, perform the following
procedure:
1. Loosen the housing rotation set screw using a -in. hex wrench.
2. Turn the housing left or right up to 180° from its original position. Over rotating will
damage the transmitter.
3. Retighten the housing rotation set screw.
Do not apply torque directly to the sensor module. Rotation between the sensor module
and the process connection can damage the electronics. To avoid damage, apply torque
only to the hex-shaped process connection.
Low side pressure port
(atmospheric reference)
Sensor Module
Process Connection