A-2
EN
Rosemount Inc
NOTE
A HART Communicator requires a loop resistance between 250 and 1100 ohms. Do
not communicate with the transmitter when power is below 12 V dc at the
transmitter terminals.
Temperature Limits
Failure Mode
The values at which the transmitter drives its output in failure mode depends on
whether it is configured to standard, NAMUR-compliant (NAMUR
recommendation NE 43, June 1997), or custom operation. The values for standard
and NAMUR-compliant operation are as follows:
Table A-5. Standard and NAMUR-Compliant Operation Parameters
Custom Alarm and Saturation Levels
Custom factory configuration of alarm and saturation level is available with option
code C1. These values can also be configured in the field using a HART
Communicator.
Operating Limit Storage Limit
°F °C °F °C
With LCD Meter
–4 to 185 –20 to 85 –50 to 185 –45 to 85
Without LCD Meter
–40 to 185 –40 to 85 –58 to 248 –50 to 120
Standard NAMUR-Compliant
Linear Output: 3.9 ≤ I ≤ 20.5 mA 3.8 ≤ I ≤ 20.5 mA
Fail high: 21.0 ≤ I ≤ 23.0 mA (Default) 21.0 ≤ I ≤ 23.0 mA
Fail low: I
≤ 3.75 mA I ≤ 3.6 mA