Designing a Liebert XD Solution
14
3.7 Liebert XDP/XDC Placement
The XDP/XDC may be placed in the critical space or in an adjacent equipment room. The allowable dis-
tance between the XDP/XDC and its connected cooling modules is determined by the piping design and
by the amount of coolant required. Refer to 3.9 - Liebert XD Coolant™ and 3.10 - Liebert XD Piping
System Design.
The maximum height of any of the main or connecting piping should be no more than 20 feet (6m)
above the top of the XDP/XDC unit. XD cooling modules should be placed as close to the same level as
possible. The differences in elevation between the highest and lowest cooling module in a system
should be no more than 6 feet (2m).
3.8 Examples of Expansion and Interlaced Connection of Liebert XD Cooling Modules
Figure 14 XDV units mounted on racks emitting 3kW of heat top view
Downflow
Cooling
Unit
Downflow
Cooling
Unit
XDVs Mounted
on Equipment Racks
Perforated
Raised
Floor Tiles
Circuit 1
Equipment Racks
without XDVs