Emerson 3051N Uživatelský manuál

Procházejte online nebo si stáhněte Uživatelský manuál pro Měření, testování a kontrola Emerson 3051N. Emerson 3051N User's Manual Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk

Shrnutí obsahu

Strany 1 - Reference Manual

Reference Manual 00809-0100-4808, Rev CAJune 2008www.rosemountnuclear.comRosemount 3051N Smart Pressure Transmitter for Nuclear Service

Strany 2

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NTOC-4Multifunction LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strany 3 - Nuclear Service

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NThe Emerson logo is a trade mark and service mark of Emerson Electric Co. Rosemount and

Strany 4 - Limitations of Remedy

Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comSection 1 IntroductionUSING THIS MANUAL The sections in this m

Strany 5 - Revision Status

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N1-2

Strany 6

Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comSection 2 Transmitter FunctionsOverview . . . . . . . . . . .

Strany 7 - Table of Contents

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-2FAILURE MODE ALARM Rosemount 3051N transmitters automatically and continuously perfo

Strany 8

Reference Manual 00809-0100-4808, Rev CAJune 20082-3Rosemount 3051N1. Security Jumper: prevents all writes to transmitter configuration.2. Local Keys

Strany 9

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-4FIGURE 2-1. Electronics Board.FIGURE 2-2. Rosemount 3051N with Optional LCD Meter.CO

Strany 10 - Rosemount 3051N

Reference Manual 00809-0100-4808, Rev CAJune 20082-5Rosemount 3051NTo commission on the bench, connect the transmitter and the communicator as shown i

Strany 11 - Section 1 Introduction

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-6Wiring Diagrams (Field Hook-up)The following diagrams illustrate wiring loops for a

Strany 12

Reference Manual 00809-0100-4808, Rev CAJune 20082-7Rosemount 3051NREVIEW CONFIGURATION DATANOTEInformation and procedures in this section that make u

Strany 13

IMPORTANT NOTICE -- ERRATA Model 3051N Product Manual 00809-0100-4808 Rev CA (6/2008) No. Affected Pages Description of Change Effect. Date 1 5-8

Strany 14

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-8NOTERegardless of the range points, the Rosemount 3051N will measure and report all

Strany 15

Reference Manual 00809-0100-4808, Rev CAJune 20082-9Rosemount 3051NFIGURE 2-5. Square Root Output Transition Point.Rerange The Range Values command se

Strany 16

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-10NOTEIf the transmitter security jumper is in the ON position, you will not be able

Strany 17

Reference Manual 00809-0100-4808, Rev CAJune 20082-11Rosemount 3051NTo rerange the transmitter using the span and zero buttons, perform the following

Strany 18

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-12Damping The process variable (PV) Damp command changes the response time of the tra

Strany 19

Reference Manual 00809-0100-4808, Rev CAJune 20082-13Rosemount 3051NTransmitter Test The transmitter Self Test command initiates a more extensive diag

Strany 20

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-14Smart transmitters operate differently than analog transmitters. A smart transmitte

Strany 21

Reference Manual 00809-0100-4808, Rev CAJune 20082-15Rosemount 3051NCalibration Overview Complete calibration of the Rosemount 3051N Pressure Transmit

Strany 22

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-16FIGURE 2-7. Transmitter Data Flow with Calibration Options.Deciding Which Trim Proc

Strany 23

Reference Manual 00809-0100-4808, Rev CAJune 20082-17Rosemount 3051NWhen performing a zero trim, ensure that the equalizing valve is open and all wet

Strany 24

Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comRosemount 3051N Smart Pressure Transmitter for Nuclear Service

Strany 25

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-18Full Trim To calibrate the sensor with a HART Communicator using the full trim func

Strany 26

Reference Manual 00809-0100-4808, Rev CAJune 20082-19Rosemount 3051NRecall Factory Trim The Recall Factory Trim commands allow the restoration of the

Strany 27

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-20NOTEUse a precision resistor for optimum accuracy. If you add a resistor to the loo

Strany 28

Reference Manual 00809-0100-4808, Rev CAJune 20082-21Rosemount 3051NHTc = URV + S (URV) Ps In this example: To calculate the corrected low trim (LTc)

Strany 29

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N2-22

Strany 30

Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comSection 3 InstallationOverview . . . . . . . . . . . . . . .

Strany 31

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N3-2Replacement equipment or spare parts not approved by Rosemount Nuclear Instruments,

Strany 32

Reference Manual 00809-0100-4808, Rev CAJune 20083-3Rosemount 3051NFIGURE 3-1. Typical Installation Flowchart.START HEREBench Calibration?Field Instal

Strany 33

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N3-4GENERAL CONSIDERATIONSMeasurement accuracy depends upon proper installation of the t

Strany 34

Reference Manual 00809-0100-4808, Rev CAJune 20083-5Rosemount 3051NNOTEFor steam service, do not blow down impulse piping through the transmitter. Flu

Strany 35 - Section 3 Installation

iiReference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NRosemount Nuclear Instruments, Inc. Warranty and Limitations of RemedyThe warranty an

Strany 36

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N3-6FIGURE 3-3. Rosemount 3051N Coplanar Flange Dimensional Drawing (Differential Pressu

Strany 37

Reference Manual 00809-0100-4808, Rev CAJune 20083-7Rosemount 3051NFIGURE 3-4. Traditional Flange Mounting Configurations with Optional Brackets for P

Strany 38

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N3-8FIGURE 3-5. Traditional Flange (Option Code H2) Dimensional DrawingTerminal connecti

Strany 39

Reference Manual 00809-0100-4808, Rev CAJune 20083-9Rosemount 3051NMounting The Rosemount 3051N Pressure Transmitter weighs approximately 6.0 lb (2,7

Strany 40

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N3-10NOTEIn steam or other elevated temperature services, it is important that temperatu

Strany 41

Reference Manual 00809-0100-4808, Rev CAJune 20083-11Rosemount 3051NFIGURE 3-6. Typical Installation Examples to Illustrate Transmitter and Impulse Pi

Strany 42

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N3-12Process Connections Rosemount 3051N connections on the transmitter flange are 1/4–1

Strany 43

Reference Manual 00809-0100-4808, Rev CAJune 20083-13Rosemount 3051NFIGURE 3-7. Power Supply Load Limitations.Wiring To make connections, perform the

Strany 44

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N3-14Grounding the Transmitter CaseThe transmitter case should always be grounded in acc

Strany 45

Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comSection 4 TroubleshootingOverview . . . . . . . . . . . . . .

Strany 46

Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comRevision StatusChanges from June 2006 to June 2008NOTEThe abov

Strany 47

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N4-2Table 4-1. Rosemount 3051N Troubleshooting Chart.The Rosemount 3051N is supplied by

Strany 48

Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comSection 5 Specifications and Reference DataNuclear Specificati

Strany 49 - Section 4 Troubleshooting

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N5-2Environmental Performance to normal operating limits as described in the “Performanc

Strany 50

Reference Manual 00809-0100-4808, Rev CAJune 20085-3Rosemount 3051NPERFORMANCE SPECIFICATIONSBased upon zero-based calibrations, reference conditions,

Strany 51 - Reference Data

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N5-4Overpressure Effect Maximum zero shift after overpressure equal to Maximum Working P

Strany 52

Reference Manual 00809-0100-4808, Rev CAJune 20085-5Rosemount 3051NFUNCTIONAL SPECIFICATIONSServiceLiquid, gas, or vaporOutput 4–20 mA, user-selectabl

Strany 53

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N5-6Span and Zero, Zero Elevation, and SuppressionZero and span values can be set anywhe

Strany 54

Reference Manual 00809-0100-4808, Rev CAJune 20085-7Rosemount 3051NFigure 5-1. Typical Smart Transmitter Response TimeMaximum Working Pressure(1)(2)Ro

Strany 55

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N5-8PHYSICAL SPECIFICATIONSMATERIALS OF CONSTRUCTIONIsolating Diaphragms316L SSTDrain/Ve

Strany 56

Reference Manual 00809-0100-4808, Rev CAJune 20085-9Rosemount 3051NOption Code Description Add:J Stainless Steel Housing 3.1 lb (1.4 kg)H2 Traditional

Strany 57

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051Niv

Strany 58

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N5-10ORDERING INFORMATIONRosemount 3051N(1) Differential, Gage, and Absolute Pressure Tr

Strany 59

Reference Manual 00809-0100-4808, Rev CAJune 20085-11Rosemount 3051NNOTEMounting Bracket option code must be specified last in the Rosemount model num

Strany 60

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N5-12ROSEMOUNT 3051N 4-20 MA/HART OUTPUT SMART PRESSURE TRANSMITTERS TYPICAL CONFIGURATI

Strany 61

Reference Manual 00809-0100-4808, Rev CAJune 20085-13Rosemount 3051NHARDWARE SELECTABLE INFORMATIONAlarm Option:  High★  Low Transmitter Security: 

Strany 62

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N5-14Figure 5-2. Rosemount 3051N Exploded View (with Coplanar Process Flange).LabelElect

Strany 63

Reference Manual 00809-0100-4808, Rev CAJune 20085-15Rosemount 3051N

Strany 64

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N5-16

Strany 65

Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comSection 6 OptionsOverview . . . . . . . . . . . . . . . . . .

Strany 66

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N6-2The meter features a two-line display with five digits for reporting the process var

Strany 67 - Section 6 Options

Reference Manual 00809-0100-4808, Rev CAJune 20086-3Rosemount 3051Na. Select 5 CM xfer fnct. Enter the transmitter transfer function for the meter. Se

Strany 68

Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comTable of ContentsSECTION 1IntroductionUsing This Manual . . .

Strany 69

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N6-44. Insert the interconnection header in the ten-pin socket exposed by removal of the

Strany 70

Reference Manual 00809-0100-4808, Rev CAJune 20086-5Rosemount 3051NFIGURE 6-2. Rosemount 3051N with Optional LCD Meter.Diagnostic Messages In addition

Strany 71

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N6-6Some non-volatile memory faults are user-addressable. Use a HART Communicator to dia

Strany 72

Reference Manual 00809-0100-4808, Rev CAJune 20086-7Rosemount 3051NOperation Normal operation messages appear on the LCD meter to confirm actions or i

Strany 73

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N6-8Option PM is a SST pipe mount bracket assembly designed for use in pipe mounting the

Strany 74

Reference Manual 00809-0100-4808, Rev CAJune 20086-9Rosemount 3051NFIGURE 6-4. Transient Protection Terminal Block (T1).

Strany 75

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051N6-10

Strany 76

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comAppendix A HART CommunicatorIntroduction . . . . . . . . . . .

Strany 77 - Appendix A HART Communicator

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-2WarningsExplosions can result in death or serious injury.• Do not remove the transmi

Strany 78

Reference Manual00809-0100-4808, Rev CAJune 2008A-3Rosemount 3051NFIGURE A-1. HART Communicator Typical Abbreviated Menu Tree for Rosemount 3051.1 DEV

Strany 79

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NTOC-2Zero Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strany 80

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-4Table A-1. Typical HART Fast Key Sequences for the Rosemount 3051 (partial listing)

Strany 81

Reference Manual00809-0100-4808, Rev CAJune 2008A-5Rosemount 3051NCONNECTIONS AND HARDWAREThe HART Communicator can interface with a transmitter from

Strany 82

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-6FIGURE A-4. Bench Hook-up(4–20 mA Transmitters).FIGURE A-5. Field Hook-up(4–20 mA Tr

Strany 83

Reference Manual00809-0100-4808, Rev CAJune 2008A-7Rosemount 3051NROSEMOUNT 275Communicator Keys The keys of the Rosemount 275 HART Communicator inclu

Strany 84

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-8Hot KeyUse this key to quickly access important, user-selectable options when connec

Strany 85

Reference Manual00809-0100-4808, Rev CAJune 2008A-9Rosemount 3051NFast Key Sequences HART fast key sequences provide quick on-line access to most tran

Strany 86

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-10NOTEOnline communication with the transmitter automatically loads the current trans

Strany 87

Reference Manual00809-0100-4808, Rev CAJune 2008A-11Rosemount 3051NROSEMOUNT 375Communicator Keys The keys of the Rosemount 375 HART Communicator incl

Strany 88

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-12Enter KeyThe enter ( ) key allows you to launch the focused item or to complete an

Strany 89

Reference Manual00809-0100-4808, Rev CAJune 2008A-13Rosemount 3051NUsing the Soft Input Panel (SIP) keyboardThe SIP keyboard allows for alphanumeric i

Strany 90

Reference Manual 00809-0100-4808, Rev CAJune 2008TOC-3Rosemount 3051NTemperature Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strany 91

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-14Fast Key Sequences The Fast Key sequence is a sequence of numerical button presses,

Strany 92

Reference Manual00809-0100-4808, Rev CAJune 2008A-15Rosemount 3051NAdd item for ALL device types or only for this ONE device type.Asks the user whethe

Strany 93

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-16Looking for a device Polling for multidropped devices at addresses 1–15.Local butto

Strany 94

Reference Manual00809-0100-4808, Rev CAJune 2008A-17Rosemount 3051NROM checksum error ONChecksum of transmitter software has detected a fault. Return

Strany 95 - Glossary

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NA-18Value out of range The user-entered value is either not within the range for the gi

Strany 96

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comGlossaryAnalog Output Trim Digital Trim operation that allows a

Strany 97

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NG-2Lower Range Value (LRV) Lowest value of the measured variable that the analog output

Strany 98

Reference Manual 00809-0100-4808, Rev CAJune 2008Rosemount 3051Nwww.rosemountnuclear.comIndexAAccess Requirements . . . . . . 3-14Alarm and Security J

Strany 99

Reference Manual00809-0100-4808, Rev CAJune 2008Rosemount 3051NIndex-2SSecurity . . . . . . . . . . . . . . . . 2-2Local Zero and Span Physical Remo

Komentáře k této Příručce

Žádné komentáře