Emerson ROSEMOUNT 5300 Specifikace Strana 29

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 106
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 28
Reference Manual
00809-0600-4026, Rev BA
December 2011
2-19
Rosemount Process Radar
Damping
User adjusted damping affects the transmitter’s ability to respond to
process changes. Therefore, the damping values + response time should
not exceed the loop requirements.
Alarm and Saturation Levels
DCS or safety logic solver should be configured to match transmitter
configuration. Table 5 identifies the alarm levels available and their
operation values.
(1)
It is assumed that the current output signal is fed to a Safety Integrity Level
2 (SIL2) -compliant analog input board of a safety logic solver. For
instructions on alarm level settings, see the Rosemount 5300 Series
Reference Manual (Document No. 00809-0100-4530), “Analog Output
(HART)” section.
NOTE
Only the High or Low Alarm Mode can be used for the Safety Function. Do not
choose Freeze Current as an error will not be announced in the current loop.
Write Protection
A Rosemount 5300 transmitter can be protected from unintentional
configuration changes by a password protected function. It is
recommended to use write protection described in the Rosemount 5300
Series Reference Manual (Document No. 00809-0100-4530), “Write
Protecting a Transmitter” section.
Site Acceptance
After the installation and configuration, proper operation of the transmitter
should be verified. A site acceptance test is therefore recommended. The
proof test outlined in this section can be used for this.
(1) In certain cases, the transmitter does not go into the user defined alarm state. For example,
in case of a short circuit, the transmitter goes into High Alarm state even if Low Alarm has
been configured.
Table 5. Alarm levels and operation values
Rosemount Alarm Level
Normal Operation
3.75 mA
(1)
(1) Transmitter Failure, hardware or software alarm in Low position.
4 mA 21.75 mA
(2)
3.9 mA
low saturation
20.8 mA
high saturation
Namur Alarm Level
Normal Operation
3.6 mA
(1)
4 mA 22.5 mA
(2)
(2) Transmitter Failure, hardware or software alarm in High position.
3.8 mA
low saturation
20.5 mA
high saturation
20 mA
20 mA
Zobrazit stránku 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 105 106

Komentáře k této Příručce

Žádné komentáře