Reference Manual
00809-0600-4026, Rev BA
December 2011
4-5
Rosemount Process Radar
Step 2. Analog Output
Signal Validation
NOTE
This section refers to 4-20 mA/HART units only.
Ensure that the loop has been set to manual mode in the DCS for the
applicable transmitter.
Use the transmitter’s built-in simulation mode to verify the analog output
settings. Output at least one arbitrary level or interface and verify that the
readings in the DCS match up.
Rosemount Radar Master > Tools > Simulation Mode
Figure 4-3. Simulation Mode -
[LT-01)
Also, or alternatively, activate the transmitter’s loop test function. Output 4, 12,
and 20 mA and verify that the readings in the DCS match up.
Rosemount Radar Master > Output > Analog Out > Loop Test
Figure 4-4. Loop test for Analog
Out 1 - [LT-01]