4 • XEV22D I&O Manual 026-1206 Rev 0 09-FEB-2011
5Absolute
Maximum Power
The XEV22D controller is capable of driving a
wide range of stepper valves; listed in Table 5-1 are
the maximum values of current that the actuator can
supply to the stepper wiring. Use the TF20D trans-
former.
Connection
Numbering
SPORLAN SAGINOMIYA
4 ORANGE ORANGE
2REDRED
3 YELLOW YELLOW
1 BLACK BLACK
5- Common GRAY GRAY
Table 4-3 - 5 to 6 Wire Valves (Unipolar)
NOTE: After making the connection, switch
the XEV controller OFF and ON to make sure
that the valve is positioned properly.
NOTE: The electrical power absorption of the
valve can be unrelated to refrigeration power
that the valve has. Before using the actuator,
read the technical manual of the valve supplied
by the manufacturer and check the maximum current
used to drive the valve to verify that they are lower than
indicated below in Table 5-1.
VALVE
TYPE
Bipolar Valves
(4 Wires)
Maximum Current
0.9A
Uni-polar Valves
(5 to 6 Wires)
Maximum Current
0.9A
Table 5-1 - Maximum Allowable Valve Current