Rosemount 3051
September 2014
www.rosemount.com
LCD transducer block
The LCD transducer block is used to configure the LCD
display meter.
Analog input block
The analog input (AI) function block processes the
measurements from the sensor and makes them available
to other function blocks. The output value from the AI
block is in engineering units and contains a status
indicating the quality of the measurement. The AI Block is
widely used for scaling functionality.
Input selector block
The input selector (ISEL) function block can be used to
select the first good, hot backup, maximum, minimum,
or average of as many as eight input values and place it at
the output. The block supports signal status propagation.
Integrator block
The integrator (INT) function block integrates one or two
variables over time. The block compares the integrated or
accumulated value to pre-trip and trip limits and
generates discrete output signals when the limits are
reached.
The Integrator Block is used as a totalizer. This block will
accept up to two inputs, has six options how to totalize
the inputs, and two trip outputs.
Arithmetic block
The arithmetic (ARTH) function block provides the ability
to configure a range extension function for a primary
input. It can also be used to compute nine different
arithmetic functions including flow with partial density
compensation, electronic remote seals, hydrostatic tank
gaging, ratio control, and others.
Signal characterizer block
The signal characterizer (SGCR) function block
characterizes or approximates any function that defines
an input/output relationship. The function is defined by
configuring as many as twenty X,Y coordinates. The block
interpolates an output value for a given input value using
the curve defined by the configured coordinates. Two
separate analog input signals can be processed
simultaneously to give two corresponding separate
output values using the same defined curve.
PID block
The PID function block combines all of the necessary logic
to perform proportional/integral/derivative (PID) control.
The block supports mode control, signal scaling and
limiting, feed forward control, override tracking, alarm
limit detection, and signal status propagation.
Control selector block
The control selector function block selects one of two or
three inputs to be the output. The inputs are normally
connected to the outputs of PID or other function blocks.
One of the inputs would be considered normal and the
other two overrides.
Output splitter block
The output splitter function block provides the capability
to drive two control outputs from a single input. It takes
the output of one PID or other control block to control
two valves or other actuators.
Backup Link Active Scheduler (LAS)
The transmitter can function as a Link Active Scheduler if the
current link master device fails or is removed from the
segment.
F
OUNDATION fieldbus Diagnostics Suite
(option code D01)
The 3051C FOUNDATION fieldbus Diagnostics Suite features
SPM technology to detect changes in the process, process
equipment, or installation conditions (such as plugged
impulse lines) of the transmitter. This is done by modeling the
process noise signature (using the statistical values of mean
and standard deviation) under normal conditions and then
comparing the baseline values to current values over time. If a
significant change in the current values is detected, the
transmitter can generate an alert.
PROFIBUS PA (output code W)
Profile version
3.02
Power supply
External power supply required; transmitters operate on 9.0
to 32.0 V dc transmitter terminal voltage. FISCO transmitters
operate on 9.0 to 17.5 V dc.
Current draw
17.5 mA for all configurations (including LCD display option)
Output update rate
Four times per second
Standard function blocks
Analog input (AI block)
The AI function block processes the measurements and
makes them available to the host device. The output
value from the AI block is in engineering units and
contains a status indicating the quality of the
measurement.
Physical block
The physical block defines the physical resources of the
device including type of memory, hardware, electronics
and diagnostic information.
Transducer block
Contains actual sensor measurement data including the
sensor diagnostics and the ability to trim the pressure
sensor or recall factory defaults.
Indication
Optional 2-line LCD display