Under normal operating conditions the
code will switch between Injection
Mode (
2
) and Normal (
1
) when not
using demand cooling.
3 Low Suction Pressure Cutout - The suc-
tion pressure has dropped below the pre-
set minimum allowable pressure (3 psi).
The compressor has been shut down and
will be available to run when the suction
pressure rises above the reset level.
The module senses voltage drop
across the pressure switch to determine
whether the low suction pressure cutout
switch is open. The low suction pres-
sure switch is in series with the pilot cir-
cuit.
4 30 Second Reset - After initial power-up or
pressing the reset button, a 30 second
initialization takes place. The flashing
numbers indicate the subnet and address
labels, and may be used to verify that all
segments of the LED function. Self-diag-
nostics are performed during this time.
The compressor will remain off during the
reset period. This is the last code dis-
played in the reset sequence.
Flashing
Description
5 Low Oil Pressure Warning - The measured
oil pressure is below the minimum accept-
able value as signaled by the sensor on
the oil pump. While the
5
is flashing, the
module is determining how much longer to
allow the compressor to run based on the
same algorithm used in the Copeland®
brand Sentronic+™ oil pressure control.
The sensor on the oil pump is an
open/closed switch, depending upon
net oil pressure. Any time the switch is
“open” prior to lockout, a
5
is displayed.
6 Low Oil Pressure Lockout - The compres-
sor is shut off due to low oil pressure.
Manual reset or remote reset is required to
enable the compressor to run again.
Remote reset must be pre-configured at
the E2 by the user.
The algorithm will shut the compressor
off after 2 minutes of continuous low oil
pressure, or when intermittent periods
of unacceptable oil pressure exceed a
33% duty cycle.
The
6
will be displayed until a manual or
remote reset takes place.
7 Motor Protection Trip - A high motor
temperature or high current condition has
shut down the compressor. The protector
must cool down and reset, or the sensors
must cool down and a minimum delay of 4
minutes must pass for automatic reset to
occur.
An open line-break protector (2D/3D
models) is determined by the current
relay in the terminal box. When line
voltage is sensed at the motor termi-
nals and there is no motor current
detected by the relay, code
7
is
displayed.
All 4D models use motor sensors. The
module shuts down the compressor
when the sensor resistance values
exceed the “trip” resistance value (this
is a function of temperature only). The
code is displayed until 4 minutes have
passed and the resistance drops
below the reset value. The compres-
sor will now run if the controller has
issued a run command.
8 Welded Contactor Warning - The
Intelligent Store™ Discus® has detected a
welded contactor condition after calling for
the compressor to shut off. The E2 will
command the compressor to run until the
condition is corrected.
The Intelligent Store™ Discus® looks
for terminal plate voltage after the con-
tactor has been called to open. If volt-
age continues to be present (on any or
all terminals) - indicating the contactor
has been welded - the E2 will send a
run command to the compressor.
The module will load the contactor so
all three legs are energized. The
8
code
will be displayed and the compressor
will run until the reset button is actuat-
ed (or remotely such as through the
E2). Manually throwing the breaker will
be required to shut the compressor
down if the contactor remains welded.
The high and low pressure switches
are in series with the pilot circuit. If they
open, they will override the module in
calling for the contactor to remain
loaded.
Manually loading the contactor after the
27
AE8-1337 R1