Quick Start Guide
21
May 2015
Europe
E1 ATEX Flameproof
Certificate: KEMA 00ATEX2143X
Standards: EN 60079-0:2012, EN 60079-1: 2007, EN 60079-26:2007
(3051SFx models with RTD are certified to EN60079-0:2006)
Markings: II 1/2 G Ex d IIC T6…T4 Ga/Gb, T6(-60 °C
≤ T
a
≤ +70 °C),
T5/T4(-60 °C
≤ T
a
≤ +80 °C)
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm. Installation, maintenance and use
shall take into account the environmental conditions to which the diaphragm
will be subjected. The manufacturer’s instructions for installation and
maintenance shall be followed in detail to assure safety during its expected
lifetime.
2. For information on the dimensions of the flameproof joints the manufacturer
shall be contacted.
I1 ATEX Intrinsic Safety
Certificate: BAS01ATEX1303X
Standards: EN 60079-0: 2012, EN 60079-11: 2012
Markings: II 1 G Ex ia IIC T4 Ga, T4(-60 °C
≤ T
a
≤ +70 °C)
Special Conditions for Safe Use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable
of withstanding the 500 V test as defined in Clause 6.3.13 of EN
60079-11:2012. This must be taken into account during installation.
Temperature class Process temperature
T6 -60 °C to +70 °C
T5 -60 °C to +80 °C
T4 -60 °C to +120 °C
U
i
I
i
P
i
C
i
L
i
SuperModule
™
30 V 300 mA 1.0 W 30 nF 0
3051S...A; 3051SF…A;
3051SAL…C
30 V 300 mA 1.0 W 12 nF 0
3051S…F; 3051SF…F
30 V 300 mA 1.3 W 0 0
3051S …A…M7, M8, or M9;
3051SF …A…M7, M8, or M9;
3051SAL…C… M7, M8, or M9
30 V 300 mA 1.0 W 12 nF 60μH
3051SAL or 3051SAM
30 V 300 mA 1.0 W 12 nF 33μH
3051SAL…M7, M8, or M9
3051SAM…M7, M8, or M9
30 V 300 mA 1.0 W 12 nF 93μH
RTD Option for 3051SF
5 V 500 mA 0.63 W N/A N/A