May 2015
28
Quick Start Guide
Special Condition for Safe Use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable
of withstanding the 500V test as defined in Clause 6.4.12 of IEC 60079-11.
This must be taken into account during installation.
China
E3 China Flameproof and Dust Ignition-proof
Certificate: 3051S: GYJ111400X [Mfg USA, China, Singapore]
3051SFx: GYJ11.1711X [Mfg USA, China, Singapore]
3051S-ERS: GYJ101345X [Mfg USA, China, Singapore]
Standards: 3051S: GB3836.1-2000, GB3836.2-2000, GB12476.1-2000
3051SFx: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010,
GB12476.1-2000
3051S-ERS: GB3836.1-2000, GB3836.2-2000
Markings: 3051S: Ex d IIC T5/T6; DIP A20 T
A
105 °C; IP66
3051SFx: Ex d IIC T5/T6 Ga/Gb; DIP A20 T
A
105 °C; IP66
3051S-ERS: Ex d IIC T5/T6
Special Conditions for Safe Use (X):
1. Only the pressure transmitters, consisting of 3051SC Series, 3051ST Series,
3051SL Series and 300S Series, are certified.
2. The ambient temperature range is (-20
~+60)°C.
3. The relation between temperature class and maximum temperature of
process medium is as follows,
4. The earth connection facility in the enclosure should be connected reliably.
5. During installation, use and maintenance of transmitter, observe the warning
“Don’t open the cover when the circuit is alive.”
6. During installation, there should be no mixture harm to flameproof housing.
FISCO
Voltage U
i
15 V
Current I
i
215 mA (IIC)
500 mA (IIB)
Power P
i
2 W (IIC)
5.32 W (IIB)
Capacitance C
i
0
Inductance L
i
0
Temperature class Temperature of process medium (°C)
T5 ≤ 95 °C
T4 ≤ 130 °C
T3 ≤ 190 °C
4801_QIG_RevMA.fm Page 28 Wednesday, May 6, 2015 1:15 PM