Quick Start Guide
9
May 2015
Figure 6. Transmitter switch and jumper configuration
A. Meter/adjustment module
B. Security
C. Alarm
Step 4: Connect wiring and power up
Use the following steps to wire the transmitter:
1. Remove and discard orange conduit plugs.
2. Remove the housing cover labeled “Field Terminals.
3. Connect the positive lead to the “+” terminal, and the negative lead to the “–”
terminal.
Note
Do not connect the power across the test terminals. Power could damage the test diode in the test
connection. Twisted pairs yield best results. Use 24 AWG to 14 AWG wire and do not exceed 5,000
feet (1500 meters). For single compartment housing (Junction Box housing), shielded signal wiring
should be used in high EMI/RFI environments.
4. Plug and seal the unused conduit connection with the provided conduit plug.
5. If applicable, install wiring with a drip loop. Arrange the drip loop
so the bottom is lower than the conduit connections and the
transmitter housing.
6. Reinstall the housing cover and tighten so the cover is fully seated with metal
to metal contact between the housing and cover in order to meet explosion
proof requirements.
The figures below show the wiring connections necessary to power a 3051S and
enable communications with a hand-held Field Communicator.
PlantWeb Junction box
NOTICE
When the enclosed threaded plug is utilized in the conduit opening, it must be installed with a
minimum thread engagement in order to comply with explosion-proof requirements. For
straight threads, a minimum of 7 threads must be engaged. For tapered threads, a minimum of
five threads must be engaged.
A
B
C
A
B
C
B
C
B
C
4801_QIG_RevMA.fm Page 9 Wednesday, May 6, 2015 1:15 PM