Quick Start Guide
29
May 2015
7. Cable entry, certified by NEPSI with type of protection Ex d IIC in accordance
with GB3836.1-2000 and GB3836.2-2000, should be applied when
installation in hazardous location. 5 full threads should be in engagement
when the cable entry is assembled onto the transmitter. When pressure
transmitter is used in the presence of combustible dust, the ingress of
protection of the cable entry should be IP66.
8. The diameter of cable should observe the instruction manual of cable entry.
The compressing nut should be fastened. The aging of seal ring should be
changed in time.
9. Maintenance should be done in non-hazardous location.
10. End users are not permitted to change any components inside.
11. When installation, use and maintenance of transmitter, observe following
standards:
GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13:
Repair and overhaul for apparatus used in explosive gas atmospheres
GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15:
Electrical installations in hazardous area (other than mines)”
GB50257-1996 “Code for construction and acceptance of electric device for
explosion atmospheres and fire hazard electrical equipment installation
engineering”
GB15577-1995 “Safe regulation for explosive dust atmospheres
GB12476.2-2006 “Electrical apparatus for use in the presence of combustible
dust – Part 1-2: Electrical apparatus protected by enclosures and surface
temperature limitation – Selection, installation and maintenance”
I3 China Intrinsic Safety
Certificate: 3051S: GYJ111401X [Mfg USA, China, Singapore]
3051SFx: GYJ11.1707X [Mfg USA, China, Singapore]
3051S-ERS: GYJ111265X [Mfg USA, China, Singapore]
Standards: 3051S: GB3836.1-2000, GB3836.4-2000
3051SFx: GB3836.1/4-2010, GB3836.20-2010, GB12476.1-2000
3051S-ERS: GB3836.1-2000, GB3836.4-2000
Markings: 3051S, 3051SFx: Ex ia IIC T4
3051S-ERS: Ex ia IIC T4
Special Conditions for Safe Use (X):
1. Symbol “X” is used to denote specific conditions of use:
For output code A and F: This apparatus is not capable of withstanding the
500V r.m.s. insulation test required by Clause 6.4.12 of GB3836.4-2000.
2. The ambient temperature range is:
Output code Ambient temperature
A -50 °C T
a
+70°C
F -50 °C T
a
+60°C
4801_QIG_RevMA.fm Page 29 Wednesday, May 6, 2015 1:15 PM