25
Reference Manual
00809-0100-4803, Rev DA
Section 4: Operation and Maintenance
April 2013
Operation and Maintenance
Figure 4-10. SuperModule connector
Note
The V-Seal (03151-9061-0001) must be installed at the bottom of the housing.
Figure 4-11. V-Seal
Attach the SuperModule assembly to the plantweb housing
1. Apply a light coat of low temperature silicon grease to the SuperModule threads and
o-ring.
2. Thread the housing completely onto the SuperModule assembly. The housing must be
no more than one full turn from flush with the SuperModule assembly to comply with
flameproof/explosion-proof requirements.
3. Tighten the housing rotation set screw using a
3
/32-in. hex wrench to a recommended
torque of 30 in-lbs (3.4 N-m).
Housing Rotation Set
Screw (3/32-inch)