Reference Manual
00809-0100-4803, Rev DA
Appendix A: Reference Data
April 2013
Specifications and Reference Data
Total performance
(1)
Models Ultra Classic Ultra for Flow
3051SMV_ _3: Differential Pressure & Temperature
3051SMV_ _4: Differential Pressure
Ranges 2 - 4 ±0.025% of span;
For spans less than 10:1,
±0.055% of span;
For spans less than 10:1,
±0.04% of reading up to 8:1
DP turndown from URL;
±[0.04 + 0.0023
(URL/RDG
(3)
)]% reading to
200:1 DP turndown from
URL
(4)
Range 5 ±0.05% of span;
For spans less than 10:1,
±0.065% of span;
For spans less than 10:1,
N/A
Range 1 ±0.09% of span;
For spans less than 15:1,
±0.10% of span;
For spans less than 15:1,
N/A
Range 0 ±0.09% of span;
For spans less than 2:1, ±0.045%
of URL
±0.10% of span;
For spans less than 2:1, ±0.05%
of URL
N/A
Process Temp.
RTD Interface
(2)
±0.67 °F (0.37 °C) ±0.67 °F (0.37 °C) ±0.67 °F (0.37 °C)
(1) Stated reference accuracy equations include terminal based linearity, hysteresis, and repeatability, but does not include analog only reference accuracy of ±0.005%
of span.
(2) Specifications for process temperature are for the transmitter portion only. The transmitter is compatible with any Pt 100 (100 ohm platinum) RTD. Examples of
compatible RTDs include Rosemount Series 68 and 78 RTD Temperature Sensors.
(3) RDG refers to transmitter DP reading.
(4) Ultra for Flow is only available for 3051SMV DP Ranges 2-3. For calibrated spans from 1:1 to 2:1 of URL, add ±0.005% of span analog output error.
Models Ultra
(1)
(1) Total performance is based on combined errors of reference accuracy, ambient temperature effect, and line pressure effect. Specifications apply only to differential
pressure measurement.
Classic and Classic MV Ultra for Flow
(2)
(2) Ultra for Flow is only available for 3051SMV DP Ranges 2-3.
3051SMV DP Ranges 2-3 ±0.1% of span; for ±50°F
(28°C) temperature
changes; 0-100% relative
humidity, up to 740 psi
(51 bar) line pressure (DP
only), from 1:1 to 5:1
rangedown
±0.15% of span; for ±50°F
(28°C) temperature changes;
0-100% relative humidity, up
to 740 psi
(51 bar) line pressure (DP
only), from 1:1 to 5:1
rangedown
±0.1% of reading; for
±50°F (28°C) temperature
changes; 0-100% relative
humidity, up to 740 psi
(51 bar) line pressure, over
8:1 DP turndown from
URL
0.005 0.0035+
URL
span
--------------
% of span
0.015 0.005+
URL
span
--------------
% of span
0.005 0.0045+
URL
span
--------------
% of span
0.015 0.005+
URL
span
--------------
% of span
0.015 0.005+
URL
span
--------------
% of span
0.025 0.005+
URL
span
--------------
% of span