Reference Manual
00809-0100-4803, Rev DA
Section 3: Configuration
April 2013
Configuration
Figure 3-16. Basicsetup tab
1. Verify the Device Tag information. The tag information is used to identify specific
transmitters on the 4-20 mA loop. This tag information may be edited.
2. Under the Flow Rate heading (Fully Compensated Mass and Energy Flow Feature Board
only), the type of flow calculation (mass or volumetric) is displayed by the indicators on
the right hand side of the box. The Flow Calculation Type may be edited by clicking on
the Configure Flow Calculation Type button. The Damping and Units of the Flow Rate
may also be edited under this heading.
Note
The flow calculation within the device uses undamped process variables. Flow rate damping is
set independently of measured process variables.
3. Under the Energy Rate heading (Fully Compensated Mass and Energy Flow Feature Board
only), the Units and Damping for the Energy Rate may be edited.
Note
Energy rate calculations are only available for steam and natural gas.
The energy rate calculation within the device uses undamped process variables. Energy rate
damping is set independently of flow rate damping or measured process variables.
4. Under the Differential Pressure heading, the Units and Damping for the Differential
Pressure may be edited.
5. Under the Static Pressure heading, the Units for both absolute and gage pressure and
static pressure Damping may be edited.