Reference Manual
00809-0100-4803, Rev DA
Section 3: Configuration
April 2013
Configuration
Note
Both absolute and gage pressure are available as variables. The type of transmitter ordered will
determine which variable is measured and which is calculated based on the user defined
atmospheric pressure. For more information on configuring the atmospheric pressure, see
“Static pressure” on page 59. Since only one of the static pressures is actually being measured,
there is a single damping setting for both variables which may be edited under the Static Pressure
heading.
6. Under the Process Temperature heading, the Units and Damping for the Process
Temperature may be edited.
7. Under the Module Temperature heading, the Units for the sensor module temperature
may be set. The sensor module temperature measurement is taken within the module,
near the differential pressure and/or static pressure sensors and can be used to control
heat tracing or diagnose device overheating.
8. Under the Analog Output heading, the primary variable can be selected from the drop
down menu and the upper and lower range values (4 and 20 mA points) for the primary
variable may be edited.
9. Under the Totalizer heading (Fully Compensated Mass and Energy Flow Feature Board
only), the Totalizer can be configured by clicking on the Configure Totalizer button. This
button allows the user to select the variable to be totalized. The Totalizer Units may also
be edited under this heading.