Reference Manual
00809-0100-4803, Rev DA
Section 3: Configuration
April 2013
Configuration
Figure 3-39. Square root output transition point
Figure 3-39 only applies to the square root output for the 3051S MultiVariable with the Direct
Process Variable Output Feature Board.
Note
For a flow turndown of greater than 10:1, it is not recommended to perform a square root
transfer function in the transmitter. Instead, perform the square root transfer function in the
control system.
3.8 Menu trees and 475 fast keys
Based on the configuration ordered, some measurements (i.e. static pressure, process
temperature) and/or calculation types (i.e. mass, volumetric, and energy flow) may not be
available for all fluid types. Available measurements and/or calculation types are determined by
the MultiVariable Type and Measurement Type codes ordered. See “Ordering information” on
page 27 for more information.
The Menu Trees and 475 Fast Keys in this section are shown for the following model codes:
MultiVariable Type M (Fully Compensated Mass and Energy Flow) with Measurement
Type 1 (Differential Pressure, Static Pressure, and Process Temperature)
MultiVariable Type P (Direct Process Variable Output) with Measurement Type 1
(Differential Pressure, Static Pressure, and Process Temperature).
The Menu Trees and 475 Fast Keys for other model codes will vary.
Slope=1
Slope=41.72
Transition
Point
Sq. Root Curve
Full Scale
Flow (%)
Full Scale
Output
(mA dc)
Sq. Root
Curve
Transition Point
Linear Section
% Pressure Input