Section 5: Troubleshooting
April 2013
Troubleshooting
Table 5-2. Transmitter troubleshooting
Symptom Corrective Actions
Transmitter milliamp output is zero Verify power is applied to signal terminals
Check power wires for reversed polarity
Verify terminal voltage is 12 to 42.4 Vdc
Check for open diode across test terminal on 3051S MultiVariable terminal
block
Transmitter not communicating with 375,
AMS, or Engineering Assistant
Verify the output is between 4 and 20 mA or saturation levels
Verify clean DC Power to transmitter (Max AC noise 0.2 volts peak to peak)
Check loop resistance, 250-1321
Loop Resistance = (Power supply voltage - transmitter voltage) / loop current
Check if unit is at an alternate HART address
Transmitter milliamp output is low or high Verify applied process variables
Verify 4 and 20 mA range points and flow configuration
Verify output is not in alarm or saturation condition
An analog output trim or sensor trim may be required
Transmitter will not respond to changes in
measured process variables
Check to ensure that the equalization valve is closed
Check test equipment
Check impulse piping or manifold for blockage
Verify primary variable measurement is between the 4 and 20 mA set points
Verify output is not in alarm or saturation condition
Verify transmitter is not in Loop Test, Multidrop, Test Calculation,
or Fixed Variable mode
Digital Variable output is low or high Check test equipment (verify accuracy)
Check impulse piping for blockage or low fill in wet leg
Verify transmitter sensor trim
Verify measured variables are within transmitter limits
Digital Variable output is erratic Check application for faulty equipment in process line
Verify transmitter is not reacting directly to equipment turning on/off
Verify damping is set properly for application
Milliamp output is erratic Verify power source to transmitter has adequate voltage and current
Check for external electrical interference
Verify transmitter is properly grounded
Verify shield for twisted pair is only grounded at one end
Transmitter output is normal, but LCD is off
and diagnostics indicate an LCD problem
Verify LCD display is installed correctly
Replace LCD display
Transmitter indicating a flow value and/or
DP value during no flow condition
Zero DP sensor
Verify DP Low Flow Cutoff setting