20 Transmitter Configuration and Use: Series 1000 and 2000 Transmitters
Connecting with ProLink II Software continued
Figure 3-8 RS-485 network connections to Model 1500 or 2500
5. Start ProLink II software. From the Connection menu, click on
Connect to Device. In the
screen that appears, specify connection parameters appropriate to your connection:
• Immediately after the transmitter is powered up, terminals 33 and 34 are available in
service port mode for 10 seconds. To connect during this period, set
Protocol to Service
Port, and set
COM port to the appropriate value for your PC. Baud rate, Stop bits, and
Parity are set to standard values and cannot be changed (see Table 3-2).
• If no connection is made during the 10-second period, the terminals are automatically
reset to the configured RS-485 communication parameters. To connect, set the connection
parameters to the values configured in your transmitter (see Table 3-2).
No
6. Click the Connect button. ProLink will attempt to make the connection.
Table 3-2 Modbus connection parameters for ProLink II
Connection type
Connection parameter Configurable (RS-485 mode) SP standard (service port mode)
Protocol As configured in transmitter
(default = Modbus RTU)
Modbus RTU
(1)
(1) Required value; cannot be changed by user.
Baud rate As configured in transmitter (default = 9600) 38,400
(1)
Stop bits As configured in transmitter (default = 1) 1
(1)
Parity As configured in transmitter (default = odd) none
(1)
Address/Tag Configured Modbus address (default = 1) 111
(1)
COM port COM port assigned to PC serial port COM port assigned to PC serial port
DCS or PLC
Add resistance if necessary
(see Step 4)
RS-485 to RS-232
signal converter
25-pin to 9-pin serial port
adapter (if necessary)
PC
RS-485 B
RS-485 A