Reference Manual
00809-0200-4801, Rev CA
July 2010
Rosemount 3051S
6-26
By default, the value of PLINE_Affect_PV_Status is “False”, meaning that the
quality of the pressure measurement will not be changed if PIL detects a
plugged impulse line. Setting this parameter to “True” will cause the status
quality to change to “Uncertain” when a plugged impulse line is detected.
Depending upon the DCS configuration, the “Uncertain” quality could be
visible to the Operator, or it could affect the control logic.
If you ever want to re-start the PIL learning process, set the parameter
PLINE_Relearn = Relearn
Note for 3051S Software Version 1.11.x (x =5, 6, or 9)
For software revision 1.11.x, after the PIL has been enabled, it is necessary to
restart the processor. The software revision can be seen via the parameter
RB_SFTWR_REV_ALL the Resource Block (see Table A-1). In AMS Device
Manager and the Field Communicator this parameter is labeled as “Software
Revision String.”
To restart the processor, the sequence depends on the host system:
For AMS Device Manager, right-click on the device, and select the menu
option Methods > Diagnostics > Master Reset. When prompted for the type of
reset, select “Processor” or “Restart Processor”.
On a Field Communicator, choose the option Resource Block > Diagnostic
Methods > Master Reset > Processor
On most other fieldbus hosts, this is done by setting the RESTART parameter
of the Resource block to the value: “Processor”
Configuration of
Detection Sensitivity
Although a few impulse line applications can be configured just by enabling
the PIL, the majority of applications will require configuring the detection
sensitivity (that is, the upper and/or lower limit on the standard deviation at
which an impulse line plug will be detected).
Figure 6-21 illustrates the basic detection sensitivity setting for PIL. In
general, a higher sensitivity means that the PIL is more sensitive to changes
in the process dynamics, while a lower sensitivity means that the PIL is less
sensitive to process dynamics changes.
Figure 6-21. PIL Basic Detection
Sensitivities