Reference Manual
00809-0200-4801, Rev CA
July 2010
Rosemount 3051S
6-30
PLINE_Learn_Sensitivity
The PLINE_Learn_Sensitivity parameters provide very specific
adjustments to the sensitivity during the learning phase. Most of the time, it
is sufficient to use the default values
Insufficient Dynamics Check: Ignores the insufficient dynamic check if
not selected. Use only when there is very low process noise. This could
result in a plugged impulse line not being detected.
10%, 20%, and 30% Stdev. Change Check: Allows for 10, 20, or 30%
change in Standard Deviation while in the learning state. If this value is
exceeded, the algorithm will stay in the verifying state until the value is
not exceeded.
Three or six Sigma Mean Change Check: Allows for a three or six
standard deviations change in the mean while in the learning state. If
this value is exceeded, algorithm will stay in the verifying state until the
value is not exceeded.
2% Mean Change Check: The mean value of the baseline calculation
cannot vary more than 2% during the learning or verifying states. If this
value is exceeded, algorithm will stay in the verifying state until the
value is not exceeded.
You may want to increase or disable one or more of these learning sensitivity
settings, if you find that the PIL continues to stay in the verification phase.
PIL Operation During operation the PIL_Status indicates the current status of the algorithm.
The valid values are:
PIL also indicates the timestamp of the last detection of a plugged impulse
line via the parameters:
PLINE_History_Timestamp
Timestamp when the last plugged impulse line was detected.
PLINE_History_Status
Indicates whether or not the PIL_History_Timestamp is available.
OK Algorithm is in the detection state, and no plugged impulse line is
detected.
Inactive The algorithm is not enabled.
Learning Algorithm is currently learning the process characteristics
Verifying Algorithm is comparing the learned baseline with the current
process.
Insufficient Dynamics The process does not have enough dynamics to detect an impulse
line plug
Bad PV Status The Sensor Transducer Status is Bad, therefore the algorithm is
paused. Algorithm will resume when a good or uncertain status
returns.
Not Licensed The ADB is not currently purchased in this device.
Plugged Line Algorithm has detected a plugged line condition. This could be
either one line or both lines plugged for a DP transmitter, or the one
impulse line plugged for a GP or AP transmitter.