Reference Manual
00809-0200-4801, Rev CA
July 2010
Rosemount 3051S
A-4
HARDWARE_
REV
52 3 N/A Read
Only
Hardware revision of that hardware that has the resource
block in it.
OUTPUT_
BOARD_SN
53 set by mfgr N/A Read
Only
Output board serial number.
FINAL_ASSY_
NUM
54 set by mfgr N/A Read
Only
The same final assembly number placed on the neck label.
DETAILED_
STATUS
55 See Table 22 E Read
Only
Indicates the state of the transmitter.
SUMMARY_
STATUS
56 0:Uninitialized
1: No repair
needed.
2: Repairable
3: Call service
center
0 E Read
Only
An enumerated value of repair analysis.
MESSAGE_
DATE
57 0 N/A Date associated with the MESSAGE_TEXT parameter
MESSAGE_
TEXT
58 spaces N/A Used to indicate changes made by the user to the device’s
installation, configuration, or calibration.
SELF_TEST 59 0:
Uninitialized
1: No test
2: Self test
1 E Used to self test the device. Tests are device specific.
DEFINE_WRITE
_LOCK
60 0:
Uninitialized
1: Everything
Locked
2: Only
physical
device locked
1 E Allows the operator to select how WRITE_LOCK behaves.
The initial value is “lock everything”. If the value is set to “lock
only physical device” then the resource and transducer blocks
of the device will be locked but changes to function blocks will
be allowed.
SAVE_CONFIG_
NOW
61 0:
Uninitialized
1: No save
2: Burn
EEPROM with
latest values
1 E Allows the user to optionally save all non-volatile information
immediately.
SAVE_CONFIG_
BLOCKS
62 0 N/A Read
Only
Number of EEPROM blocks that have been modified since
last burn. This value will count down to zero when the
configuration is saved.
START_WITH_
DEFAULTS
63 0-4 1 E 0 = Uninitialized
1 = do not power-up with NV defaults
2 = power-up with default node address
3 = power-up with default pd_tag and node address
4 = power-up with default data for the entire communications
stack (no application data)
SIMULATE_IO 64 0:
Uninitialized
1: Off
2: On
0 E Read
Only
Status of Simulate jumper/switch
SECURITY_IO 65 0:
Uninitialized
1: Off
2: On
0 E Read
Only
Status of Security jumper/switch
SIMULATE_
STATE
66 0 - 3 1 E Read
Only
The state of the simulate jumper
0 = Uninitialized
1 = Jumper/switch off, simulation not allowed
2 = Jumper/switch on, simulation not allowed (need to cycle
jumper/switch)
3 = Jumper/switch on, simulation allowed
Parameter Index Valid Range Initial Value Units Other Description