Reference Manual
00809-0200-4801, Rev CA
July 2010
B-9
Rosemount 3051S
Vibration Effect Less than ±0.1% of URL when tested per the requirements of IEC60770-1
field or pipeline with high vibration level (10-60 Hz 0.21mm displacement peak
amplitude / 60-2000 Hz 3g).
For Housing Style codes 1J, 1K, 1L, 2J, and 2M:
Less than ±0.1% of URL when tested per the requirements of IEC60770-1
field with general application or pipeline with low vibration level (10-60 Hz
0.15mm displacement peak amplitude / 60-500 Hz 2g).
Power Supply Effect Less than ±0.005% of calibrated span per volt change in voltage at the
transmitter terminals
Electromagnetic
Compatibility (EMC)
Transient Protection
(Option T1)
Meets IEEE C62.41.2-2002, Location Category B
6 kV crest (0.5 s - 100 kHz)
3 kA crest (8 × 20 microseconds)
6 kV crest (1.2 × 50 microseconds)
Meets IEEE C37.90.1-2002 Surge Withstand Capability
SWC 2.5 kV crest, 1.0 MHz wave form
3051SMV_ _ 1 or 2
3051SF_1, 2, 5, or 6
DP Sensor: Zero shifts up to ±1.25 inH
2
O (3,11 mbar), which can be zeroed
Span: no effect
GP/AP
Sensor:
Zero shifts to ±2.5 inH
2
O (6,22 mbar), which can be zeroed
Span: no effect
3051S_L With liquid level diaphragm in vertical plane, zero shift of up to ±1 inH
2
O (2,5 mbar). With diaphragm in
vertical plane, zero shift of up to ±5 inH
2
O (12,5 mbar) plus extension length on extended units. All
zero shifts can be zeroed.
Span: no effect.
Models Ultra, Ultra for Flow, Classic and Classic MV
Meets all relevant requirements of EN 61326 and NAMUR NE-21.
(1)(2)
(1) NAMUR NE-21 does not apply to wireless output code X.
(2) 3051SMV and 3051SF_1, 2, 3, 4, 5, 6, 7 requires shielded cable for both temperature and loop wiring.