Reference Manual
00809-0200-4801, Rev CA
July 2010
A-3
Rosemount 3051S
MAX_NOTIFY 31 7 N/A Read
Only
Maximum number of unconfirmed notify messages possible.
LIM_NOTIFY 32 0 to
MAX_NOTIFY
MAX_NOTIFY N/A Maximum number of unconfirmed alert notify messages
allowed.
CONFIRM_
TIME
33 640000 1/32
millisec
The time the resource will wait for confirmation of receipt of a
report before trying again. Retry will not happen when
CONFIRM_TIME=0.
WRITE_LOCK 34 1: Unlocked
2: Locked
1 E If set, no writes from anywhere are allowed, except to clear
WRITE_LOCK. Block inputs will continue to be updated.
UPDATE_EVT 35 N/A This alert is generated by any change to the staic data.
BLOCK_ALM 36 N/A The BLOCK_ALM is used for all configuration, hardware,
connection failure or system problems in the block. The cause
of the alert is entered in the subcode field. The first alert to
become active will set the Active status in the Status attribute.
As soon as the Unreported status is cleared by the alert
reporting task, another block alert may be reported without
clearing the Active status, if the subcode has changed.
ALARM_SUM 37 N/A The current alert status, unacknowledged states, unreported
states, and disabled states of the alarms associated with the
function block.
ACK_OPTION 38 0: Auto Ack
Disabled
1: Auto Ack
Enabled
0 N/A Selection of whether alarms associated with the block will be
automatically acknowledged.
WRITE_PRI 39 0 - 15 0 N/A Priority of the alarm generated by clearing the write lock.
WRITE_ALM 40 N/A This alert is generated if the write lock parameter is cleared.
ITK_VER 41 set by FF 5 N/A Read
Only
Major revision number of the interoperability test case used in
certifying this device as interoperable. The format and range
are controlled by the Fieldbus Foundation.
DISTRIBUTOR 42 "Rosemount" 0X26 E Read
Only
Reserved for use as distributor ID. No Foundation
enumerations defined at this time.
DEV_STRING 43 0 to
0xFFFFFFFF
0 N/A This is used to load new licensing into the device. The value
can be written but will always read back with a value of 0.
XD_OPTION 44 E Read
Only
Indicates which transducer block licensing options are
enabled.
FB_OPTION 45 E Read
Only
Indicates which function block licensing options are enabled.
DIAG_OPTION 46 E Read
Only
Indicates which diagnostics licensing options are enabled.
MISC_OPTION 47 E Read
Only
Indicates which miscellaneous licensing options are enabled.
RB_SFTWR_
REV_MAJOR
48 set by build N/A Read
Only
Major revision of software that the resource block was created
with.
RB_SFTWR_
REV_MINOR
49 set by build N/A Read
Only
Minor revision of software that the resource block was created
with.
RB_SFTWR_
REV_BUILD
50 set by build N/A Read
Only
Build of software that the resource block was created with.
RB_SFTWR_
REV_ALL
51 set by build N/A Read
Only
The string will contains the following fields:
Major rev: 1-3 characters, decimal number 0-255
Minor rev: 1-3 characters, decimal number 0-255
Build rev: 1-5 characters, decimal number 0-255
Time of build: 8 characters, xx:xx:xx, military time
Day of week of build: 3 characters, Sun, Mon, …
Month of build: 3 characters, Jan, Feb.
Day of month of build: 1-2 characters, decimal number 1-31
Year of build: 4 characters, decimal
Builder: 7 characters, login name of builder
Parameter Index Valid Range Initial Value Units Other Description