Reference Manual
00809-0200-4801, Rev CA
July 2010
Rosemount 3051S
6-31
Plugged Impulse Line
Configuration in EDDL
Host systems that support Electronic Device Description Language (EDDL)
may use labels for the PIL configuration parameters that are slightly different
from the Fieldbus parameter names described previously in this section.
Table 6-2 below shows the correspondence between the fieldbus parameter
names used in this document, and the labels used in EDDL hosts, such as
AMS Device Manager.
Viewing the Indication of
a Plugged Impulse Line
When a plugged impulse line is detected, a PlantWeb alert is generated, and
this alert can be seen in AMS Alert Monitor. Also (optionally), using the “Affect
PV Status” parameter, the status of the pressure measurement can be made
to change from “Good” to “Uncertain” when the line plug is detected.
Dependent upon the DCS configuration, the uncertain status of the
measurement may be indicated within the Operator Interface.
Fieldbus Parameter Name EDDL Label(s)
PLINE_ON Plugged Line
PLINE_Learn_Length Learning Cycle
PLINE_Sensitivity Sensitivity
Detection
Detection Sensitivity
PLINE_Affect_PV_Status Affect PV Status
PLINE_Relearn User Command
PLINE_Auto_Relearn Auto Relearn
PLINE_Relearn_Threshold Relearn Threshold (% of URL)
PLINE_Learn_Sensitivity Learning Sensitivity
PLINE_Detect_Length Detecting Cycle
PLINE_Detect_Sensitivity Custom Sensitivity
PLINE_Single_Detect_Sensitivity DP Single Line Custom Sensitivity
PLINE_Status Plugged Impulse Line Detection Commands
Plugged Impulse Line Detection Status
Plugged Impulse Line Status
PLINE_History_Status Plugged Impulse Line History - Status
PLINE_History_Timestamp Plugged Impulse Line History – Time Stamp